why designer use kva rating instead of kw in transformer
rating???????????????
Answer Posted / amolkarne
x'mers,UPS,DG etc are rated in KVA beacause at the time of
manufacturing manufacturer is unknown about the type of
load (inductive,capacitive or resistive)that perticular m\c
is going to suypply.so there is no question of pf to be
considerd to give it's rating in KW...........
KVA = KV X Amps -(1)
KW = KV X Amps X P.F. -(2)
it gets more clear by looking towards above formulae
| Is This Answer Correct ? | 21 Yes | 6 No |
Post New Answer View All Answers
A 100 kVA , 400 v/250 kv testing transformer has 8% leakage reactance and resistance on 100 KVA base . A cable has to be tested at 500 kv using the above transformer as a resonant transformer at 50 hz . if the charging current of the cable at 500 kv is 0.4 A find the series inductance required . Assume 2% resistance for the inductor to be used and the connecting leads . Neglect dielectric loss of hte cable . what will be the input voltage to the transformer ?
how can tell us the AC indoor or outdoor which Tr and formulls
in control scheme dc logic wiring commonly using negative loop,what is the reason?if we use positive looping what will happen?
what is the function of gss in the dg set.
In india, according to trade theory above 5 HP motor reqired star delta starter. But we R connect 11 KV motor with 14MW in Direct to line ( With VCB starter combination) Can U Guess, How it is possible ?????
How to Decide the Location of Earth pit for Compressor in Oil Depo? and How to measure the resistance of earth pit Pls explain me with the help of Circuit Diagram?
Advantages of using generator circuit breaker (GCB) scheme in a power station ?
What are the classifications of oscillators?
tell me about eletrical contractor
What is the meaning of loop in transformer
Distribution transformer we provided 2 separate earthing pit for Body and 2 separate earthing pit for neutral,we can not connect separate body earthing pit to other earthing pit but we do metal glanding in secondary side cable termination in both side, transformer and PCC panel (LT Panel), is this safe for transformer and other equipment?
What are the causes of having an rmu explode after installation? And how do u treat the bushings of an rmu?
please send me previose rrb junior engineer qustion papers
How do apply electrical 'c'license......pls advice
why connecting surge unit in contactor coil