Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

why designer use kva rating instead of kw in transformer
rating???????????????

Answer Posted / amolkarne

x'mers,UPS,DG etc are rated in KVA beacause at the time of
manufacturing manufacturer is unknown about the type of
load (inductive,capacitive or resistive)that perticular m\c
is going to suypply.so there is no question of pf to be
considerd to give it's rating in KW...........
KVA = KV X Amps -(1)
KW = KV X Amps X P.F. -(2)

it gets more clear by looking towards above formulae

Is This Answer Correct ?    21 Yes 6 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

The principle of switching circuits for different types of batteries in application of storage systems

2012


Starting current of a 10 HP induction Motor is ______ time’s full load current.

2997


What is the comparison of PILC and XLPE cable

2233


what is a bus riser in power system and why it is used

46363


How to calculate per unit impedance of transformer?

2274


List the disadvantages of constant k filters?

1761


What will happen if i used 11KV earth ht kit to 11 KV / 11 KV cable termination?

1476


In ht capacitor ckt we are using LBS Panel it having isolator with fuse, one of HT fuse flash over, so what is reason behind this event.

2145


What are chief characteristics of state-space method and its techniques ?

2212


pre arcing time of ehv breaker

2183


For refrigerators the motor current is raised beyond its rating on both conditions when the voltage of the system is more(say 270v) than the rated voltage(220v) as well as when the voltage of system is less(say 160v) than normal voltageof 220v, why explain?

2034


Pl.brief me any electrical major fault you have rectified.

2006


what is a bus post insulator? explain its application in a substation.

12667


Dear Respected sir how to test ABB REX521 protection relay by relay tester.

2793


why normally Generator rating are between 11Kv to 22Kv?

4773