Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

What is the difference between double compression

Answer Posted / shirsendu saha

I don't think any of the above answers are completely correct.
Single compression and double compression glands are used on
the basis of area classification.those who are affiliated
with oil and gas sector they will easily understand about
area classification.in zone 0 where the presence of
hydrocarbon is obvious (IIC)double compression gland is used
because the flame path in case of double compression gland
is much more than in case of single compression gland. the
logic behind this is that if there is any explosion inside
the terminal box of the motor no flame should be able to
come out through the cable gland in order to prevent fire
hazards but where there is no presence of hydrocarbons i.e
no danger of fire hazards (IIA/ IIB)single compression glads
are used. it has nothing to do with mechanical strength.
even in case of lighting fixtures used in IIC zone double
compression glands are used.

Is This Answer Correct ?    89 Yes 13 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Incoming line 11kv And transformer capacity is 2500kva. Consumption load is 1300A. Then fuse capacity is 11kv line.

1667


Why air circuit breaker off due to power failure?

1202


what types of cable used in underground coal mining?

1472


Could the power factor on electrical system can affect the registration of the kwhr meter or the CT/PT? 

1956


Write down the design procedure of commutaj.

2122


is it possible to turn on the single phase star delta on delay timer using 24 v dc ?

2029


what is there inside an inverter and how it works?

1830


How time response of the system is divided?

1185


15hp motor wound by 0.9mm & 0.95mm magnet wire. at no load test it draw 4.2A current. Another motor with same condition draw 9.2A current. How can that occur? pls help

1567


Define delay time.

1083


Why MCCB is Getting tripped sometimes when there is no load in the Midnight ?

1968


What is the formula for selecting the cabels according to load? How to calculate what sq.mm cabel to be used?

1487


How maesure earth neutral value & how much maximum value value required in between earth & neutral.

2065


what are the Alarm, Trip & Safety equipment (Issues) present in Power Transformers pls Mail it to ashokbabunhce@gmail.com

1903


If a surge divertor is required to be protected by 32 amp C Curve Circuit breaker does this limit the amount of protection from surges that you will acheive

1788