i have 80cm water tank.how can i use DPT as level
mesurment.pls give specs for that..?
We have air comp.from that moisture comeout to one tank.i
want to mesure level of water in that tank and then after
operat one sov to dicharge water after high level.
Answer Posted / ashish khatana
TAKE TWO TAPINGS, ONE AT 5CM (HP SIDE)ONE AT 75 CM (LP
SIDE). NOW CONNECT THE DPT AS PER HP AND LP CONNECTION AND
IN Tx. ALSO DEFINED THE LSV AND USV IN Tx. IT WILL GIVE U 4
MA AT 5 CM AND 20MA AT 75 CM OF THE TANK LEVEL.
NOW THE SAME THING U CAN DO FOR THE COMP. MOISTURE LEVEL.
TO OPERATE SOV U HAVE TO USE THE ANALOG SIGNAL COMING FROM
DPT AND WITH USE OF THIS U HAVE TO GENERATE A DO COMMAND
(24V). THIS COMMAND WILL DIRECTLY GO TO SOV(24 V) WHEN
LEVEL IS HIGH.
SUPPOSE DPT TAG IS (PI01)
SET PI01.HH AT 75 CM.. AND USE THIS SIGNAL TO GENERATE THE
DO FOR SOV USING A SWITCH LOGIC IN DCS
| Is This Answer Correct ? | 9 Yes | 2 No |
Post New Answer View All Answers
How to calibration coriolis flow meter?
this site is owned by an nonsense
what is surge and how is it prevented, what is the purpose of bypass valve across AS valve.
What are the maximum packet size of: a) HART b) Profibus DP c)Profibus PA d) DeviceNet e) Foundation Fieldbus
send me last 5 years questions asked in rrb chennai, for section engineer
Regarding , there is an air cooler which control the fans(50% of AV FANS) by temperature in outlet , and the louver of Air cooler is controlled by HIC from control system , So if on Air cooler we will consider 2 individual I/P converter or positioner?
Why use ball valves on Gas pipelines instead of gate & or globe valves...means basic diffrence or use of these valves..how designers knows this type of valve with rating is required...
Identification of control valve parts.
Which type of pressure can be measured by primary elements?
Please tell me details about Sox,Nox,SWAS analyser????
what is the calibration procedure for transweigh make weigh feeder?
Introduce yourself which is not present in your biodata?
What is the principle of capacitance type level transmitter?
while i check zero check for dp flow transmitter some fluctuating came (0 to 458 kg/h) what is the reason?
what is the usage of QDV & VOLUME BOOSTER