What are the difference between C-Curve and D-Curve for
MCB's.
Answer Posted / h.shastri
almost all answer is somewhat correct
the main thing is to selection of proper MCB which matches
with your equipments and instruments
for that i'd like to give you an case study...
let's Assume one Heating Control Action
suppose i am using a 1ph. heater of 1200 Watt (5.2 Amps)
now i am controlling heating action using an SSR or
relay/contactor
now if i will select SSR (relay/contactor)'s rating =6 amps
and i also impliment MCB of 6 Amps.b-curve
then in case of heater failer or implimenting different
rating's heater,
assume that circuit is taking some higher current say, 10
Amps in such my SSR(relay/contactor)will damage due to high
load current which is higher then their rating of 6 Amps
but MCB will not trip instently ( it trips after 5-10 min.
because load current is not more then 12 Amps)
in this case MCB will not protect your instruments.
now if i'll decrease MCB's rating it will starts tripping
on and on.....
if i'll select MCB more then 6 Amps again in this case MCB
will not trip
so that, if i m using b curve 6 Amps MCB then i must select
SSR(relay/contactor)'s rating more then 12 Amps say 15Amps.
then and then problem will be solve.
also if i will use MCB of C or D curve then Again i have to
choose instruments which has atleast 3-5 times higher
rating of MCB.
| Is This Answer Correct ? | 66 Yes | 12 No |
Post New Answer View All Answers
what is working process of star delta controlling circuit ?
CAN ANYBODY PLEASE TELL ME HOW TO DESIGN A SERIES REACTOR FOR LIMITING SHORT CIRCUIT FAULT CURRENT??
What is the accepted limit to increase the choosen transformer capacity over the load and why ?
What is the end effect of linear induction motor ??
I would like to know that the fault curretn at base load and at 10% generation will be same? Fault level of BUS remain same with different generation?
What is MSL designation of a motor and same may be provided in details.
A cotter joint is generally used to transmit
describe the fully control circuit diagram of ac drives
how to decide the panel size like MDB ,SMDB PANEL SIZES
Could the power factor on electrical system can affect the registration of the kwhr meter or the CT/PT?
Define average demand?
I have a current transformer with 1 main reading meter with transformer outside the building and a control panel having 5 CT reading meters with black round coils inside the building. I want to know, A) when current pass through the Transformers, will the current be reduced or be the same and after that B) when current pass through the CT meters with black round coils, will the current be reduced or be the same. C) in the above process will the reading of the main meter be same or different, from the total reading of all the 5 CT meters.
Dear All, I am new in construction company , my boss ask a question at time of interview , If we have 60MW generation and Single Power Transformer step-up we have. if CMR 50/60MVA , ONAN, ONAF respectively , is it sufficient or not ? for that much power to transfer,
Why Neutral Isolation is required?
what is proper capacitor placement? How to evaluate capacitor size?