If hart communicator provide 4-20ma source to any
transmitter during the callibration?
Answer Posted / paresh koradia
Communicator does not provide the 4-20ma or any kind of
supply voltage.However, we can force the output (4-20ma) of
the transmitter by communicator. The transmitter requires
an external power supply and the communicator just
connected parallely is used to either read the diagnostic,
process or else data from the transmitter plus to write
certain data like tag no., tuning parameters, calibration
data, ranges, etc.
| Is This Answer Correct ? | 12 Yes | 1 No |
Post New Answer View All Answers
What is instrumentation control?
How to Calibrate Level Switch in field
Draw symbols of the following :
What is the diffrence between ff tx and non ff tx
What is exact difference between the panel earthing and system earthing in DCS system. What is the value of resistence.
KAlman filter code for two dimension?
what is interface level and how it is calibrate?
I want to buy a seal kit of a pneumatic power cylinder.But I don't know it's specification.So please help me to know its specification.
in valve is constructed as per SME B 16.34, then which standard is used for fire testing of valve?.
tell me the field & lab calibration procedure step by step with diagram of pressure gauge, pressure switch, pressure transmitter, temperature switch, level switch, flow switch, flow transmitter, temperature transmitter, temperature indicator, flow indicator, level indicator, control valve, thermocouple, pressure indicator (digital & analogue),
What is cut off relay? And why use in PLC and DCS?
plz send me general of ongc
Please tell me details about Sox,Nox,SWAS analyser????
How to calibrate level transmitter with use of HART?
what is wave length were using ?