why the rating of a transformer in kva not in kw.

Answer Posted / naveen

kVA is the unit for apparent power. Apparent power consists
of active and reactive power. Active power is the share of
the apparent power which transmits energy from the source
(generator) to the user. Reactive power is the share of the
apparent power which represents a useless oscillation of
energy from the source to the user and back again. It occurs
when on account of some »inertia« in the system there is a
phase shift between voltage and current. This means that the
current does not change polarity synchronous with the
voltage. But the heat generated in a winding as well as the
eddy current losses generated in a transformer core depend
on the current only, regardless of whether it aligns with
the voltage or not. Therefore the heat is always
proportional to the square of the current amplitude,
irrespective of the phase angle (the shift between voltage
and current). So a transformer has to be rated (and
selected) by apparent power.

Is This Answer Correct ?    8 Yes 4 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is formula for zero phase sequence of nuetal earthing transformer of 6.6 kv

1808


how to select size of hardware for linking aluminium busbar is it depend on area of busbar or current flowing through bus bar

1631


please forward me the type of questions which would rise while me attending to 33KV Electrical License to my mail ID:vadrevu_raghava@yahoo.co.in

1645


How do I calculate/select Droop CT ratio for various capacity of generators?

3208


What is class ab operation?

720






1. What is the exact formula for one weber? for example,(one ampere = one coulomb electron of electrons crossing a point of conductor at one second. i.e, 1A=1Q/1sec)

1522


please send privious years question papers of jindal steel and power ltd.My e mail id is rajanikant.sngh@gmail.com

1729


How do you compute voltage drop and cable size over distance?

1847


1.4 What is meant by CT knee point voltage and how would you determine it

1287


How to select the gauge of wire for winding of motors? How to select number of turns for winding of three phase induction motor?

2353


If oil and air can withstand a high MeV when used as an insulator in a transformer, what are the values of how high for each material?

1442


If the rated speed of a d.c. Shunt motor is1440 r.p.m, which method of speed control would you suggested to obtain a speed of 1500 r.p.m?

812


how to select the automotive wire size by mathematical calculation. for xenon headlamp with ballast. the ballast given data voltage 10-17v,current permenant 6amp, run up phase is 15amp, peak at swicth on max 400micro sec is 40amp.the sum of cable resistance is 150mohm.please provide referenc document if any for relating the peak at switch on current,time & wire wire size

2021


what is magnetizing current test in power transformer

2282


# 4 hi friends i m from electrical branch and seeking for tech. + apti. both papers of hpcl plz get it available as soon as possible my email id is sumit_lig189@yahoo.co.in

1663