Answer Posted / thowsif_emerson
The first-pole-to-clear-factor (kpp) is dep
The first-pole-to-clear-factor is used for calc
three-phase faults. In general the following cases apply: -
kpp = 1.3 corresponds to three phase faults in systems with
an earthed neutral. - kpp = 1.5 corresponds to three phase
faults in isolated
- kpp = 1.0 corresponds to special cases, e.g. two-phase
railway systems.
arth in a syst
A special case is when there is a three-phase fault without
involving e
not normally considered in the standards.
| Is This Answer Correct ? | 6 Yes | 8 No |
Post New Answer View All Answers
what is allowable ac mixing in dc
How PADO software increase the efficiency of power plant?
Which type of questions well asked. ?
what is the defination of Cable database? What are the points are considered while preparing cable database? Is there any sample available for cable database?
sir pls tell me . our ct specifications are 120/5 ,2 core , 0.2 and 5p10 class , 30va and 30va buden. insted of 30 va i want use 15 va. can i use?
Will any motor burn if voltage provided is lesser than the rated voltage???? If yes, then how is speed control possible with voltage control
how many load we can take for lighting
Why we are going for converter transformers for DC drives application instead of distribution transformer?
Is Transol transformer oil comparable to nynas nytro libra?
What is the fault or needs to be done when frequency in ac drives is not changing?
how many Classification of fire extinguisher
3 phase induction motor connection star or delta while using ac drive motor is .75 to 5.5 kw
What is FM200 Gas??Applications........
If VFD is On but no starting commond on it. so how many outpout voltages of VFD
If the earth is a good conductor of electricity, why don't people get shocked every time they walking on earth?