What is the harm if we install primary side 11 KV VCB at a
distance of one Km from the 11/3.3KV 12.5 MVA transformer
through 11 KV cable.
Answer Posted / khor
No harm at all,but finding cable is a problem.11kv cable
supply for 12.5MVA must carry 650A per phase which is too
big for most standard cables.Standard VCB are 630A,1250A &
2000A,2500A.The more commonly available large size 3-core
300sqmm 11kv copper(450Amp) or alluminium conductor
cables,which is still flexible and can be transported &
coiled in drums of 250 to 300 metre lengths.There are
500sqmm 11kv 1-core xlpe/awa/pe cables available.
If you use only one transformer which is more
economical,the 3.3 KV side will be more than 2187Amp(plus
additional amp on losses and fans).While you can find 2500A
VCB,you will need more than 600sqmm copper conductors which
is not flexible/practical.
For the better/optimum design,seperate the final 415V and
3.3KV loads required and divide them into 2 groups and look
at the MVA and size them in seperate circuits.If 12.5 MVA
is all in 3.3Kv then employ 2 Main transformers where you
are not putting all the eggs in one basket.You need to
remember to look at the short circuit capacity( in KA 1 sec
or 3sec ) of the cables in circuit where small MVA is
involved.For e.g.1 MVA needs 52A @11KV but you cannot use
35sqmm cables,as it will blow like a fuse during fault
situation.
1 km of cables will have quite enough impedence to
limit/lower the fault level of the system.Protection of
this cable can be done with Pilot protection relays on
sending and rereving end,operated by class X CTs mounted in
the 11KV VCB panels.1 KM of Pilot wires of 2.5 sqmm 7-cores
alomg this cable is requird.So far I am assuming that it is
uderground cable is used.For Ariel Bundle Cable,3-core 185
sqmm aluminium is available.
| Is This Answer Correct ? | 3 Yes | 2 No |
Post New Answer View All Answers
1.what is meaning of curve into a mcb. 2.what is basic reason changing of curve
at work we have a 3 phase motor but on testing one phase isnt getting a reading. it runs 24 hours a day all week. stops and starts well no noise or heating. the phase isnt down to earth.is it just a bad meter reading or not? phases one and three came up with a resistance reading of 0.4 but phase 2 couldnt get anything shows up as open circuit.
what will happen reduce the transformer voltage from 415v to 406v, is it save the energy,? are this methodis good to reduce the energy.?
why effective resistance should be more than static resistance in transmission line?
What is resistance of 50meters, 16sq.mm, single core copper cable?
Why do you have to use Protecion relay with the function MTB ( Mechanical Trip Button ) for electrical system.
What is polar plot?
What are the causes of having an rmu explode after installation? And how do u treat the bushings of an rmu?
when we have to use UPF wattmeter and LPF wattmeter? what is the difference between UPF and LPF wattmeter in terms of construction?
1. Design a counter which counts 0, 4, 8, 2, 6, and repeats using: 1.a using JK flip flops 1.b using T flip flops 1.c using D flip flops
whats the application of voltage regulation? and whats the voltage regulation's device?
I WANT TO know WHICH WAY IS BETTER FOR CONNECTION BETWEEN POWER TRANSFORMER AND MAIN DISTRIBUTION PANEL. 1-IS BETTER WE USE CABLE? 2-IS BETTER WE USE BUS DUCT? my transformer rate power is 2500KVA
what is physical distance of isolator to VCB in 33/11kv sub stations
i applied for the ap transco please forward the freqventley asked QA
What is a commutator?