Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

How would we calculate the no of earthing pits required
for motor /panel

Answer Posted / syed rafiudeen

18. The GI conductor sizes shall be as listed below.

(1). HT switchgear, structures, cable trays & fence, rails,
gate and steel column
50 X 6 mm

(2). PCC & MCC EARTH PITS
50 X 6 mm

(3). DB
25 X 6 mm

(4). Motor rated above 55 KW & above
50 X 6 mm

(5). Motor rated above 22 KW & up to 55 KW
40 X 6 mm

(6). Motor rated above 5.5KW & up to 55KW
25 X 6 mm






(7). Motor rated up to 5.5 KW
8 SWG. GI wire

(8). Lighting panels & local panel
25 X 6 mm

(9). Control & relay panel
25 X 6 mm

(10). DG frame, excites
50 X 6 mm

(11). DG & TX’mer neutral
50 X 6 mm cu flat

(12). TX’mer body
50 X 6 mm

(13). Push button station
8 SWG. GI wire

(14). Receptacles & welding outlets
8 SWG. GI wire

(15). Lightning Arrestor
25 X 3 mm copper

(16). PLC & WF panels
25 X 3 mm copper

Is This Answer Correct ?    16 Yes 5 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

given data are load current & power factor cable core size? plz any one update the calculation formula

1846


draw vector diagram and +ve,zero sequence diagram of symmetrical three phase fault.

1977


distribution is maximum done by a)radial b)network c) parallel d)b & c

1896


how the phase convertor changes the no. of phases

1945


What is an Air COmpressor

2193


IF DISTANCE IS 100METERS B/W AMP.METER AND CURRENT TRANSFORMER WHAT WILL BE AFFECT IN ACCURACY .METER CAN SHOWING ACCURATE CURRENT OR NOT IF NOT WHAT CAN I DO TO GET 100% ACCURACY.

1785


How to calculate main incomer rating of APFC Panel ? Let's say i want to find main incomer for 11kV, 1000kVAR Panel.

1869


What is the necessary and sufficient condition for stability.

1085


Pls mail me utility & Dg related question with answer

1748


Explain about 3 phase motor fault current calculation with examples?

2875


How u can give the overload setting to any motor protection relay for a HT motors with formula and Example?

2134


What is the function of a neutral reactor.

1802


The power factor of the fixed load is 0.8, now the p.f is varying from 0.8 to 0.5.

1934


What is a difference between indoor transformer and outdoor transformer of same rating

5750


what happen when increase or decrease size of lamp,light.glass.

1875