Answer Posted / thwosif_emrson
How to find out Iron & Copper lossed in transformer:-
1>Iron Losses:-
Iron losses are due to hysteresis and eddy-current loss
produced by the alternating magnetic flux in the iron core.
The iron losses are almost independent of the load and thus
are considered to be constant at all loads.
In order to determine the iron loss, one winding of the
transformer (whichever is the most convenient) is open
circuited. A voltage is applied to the other winding and
the power (watts) in this circuit is measured. This power
represents the iron losses. Copper losses under these
circumstances are negligible.
2>Copper Losses:-
Copper losses are the heat losses in the windings due to
the electrical resistance of the windings. The copper
losses are proportional to the square of the current and
therefore to the kVA output. These losses can be calculated
from the design data but can also be measured by a test.
This test is known as the short circuit test for copper
losses.
The short circuit test is carried out by short circuiting
one winding, thus causing the transformer to behave like a
coil having a leakage impedance equal to that of both
windings. A low voltage is applied to the open winding
sufficient to circulate full load current through the open
winding due to transformer action in the short-circuited
winding. Under these conditions, the flux set up in the
core is so small that iron losses can usually be neglected
and the wattmeter would give the total copper loss.
| Is This Answer Correct ? | 39 Yes | 6 No |
Post New Answer View All Answers
State the types of distortions in amplifier?
I want to ask that is there any relation between current denesity of copper and material purity. also is ther any standard which defines the standard current denesity of material.
Define cut-off rate?
Is there a diode made that works with AC 120 volt 20 amp? If so can it completely stop all current flow in 1 direction at all times?
why we are using Load factor?
A 50Hz,4-pole,3-phase,star-connected synchronous motor has a synchronous reactance of 12ohmsper phase and negligible armature resistances.the excitation is such as to give an open-circuit voltage of 13.2kilovolt.the motor is connected to 115kilovolt, 50hertz supplying. what maximum load can be the motor torque,line current and power factor?
What is the voltage gain or transfer function of amplifier?
How to configure the drives in PLC, through Profibus commnication. And to how to address it?
i have applied for the post of RRB section engineering chennai board please send me previou papers and solved answer. my mail id jagarapusrinivas@gmail.com
is this the formula of building wiring to get the main breaker.Watts/volts*.8%+higher motor*(25%)=ampere. yes or no or send the correct formula for building wiring.
what is the main function of capacitors in mccs.
Please elaborate th´evenin’s theorem?
what are the range of memory address in plc for L&T lx7 4A
why not starting switch first connect in direct on line starter?????
what's the requirement of Dy11d0 connection of 3 phase transformer?what's use of it?