How much pole motor can be desion for 415 volt ,50 hz.Power
supply. in pratical condition .
Prakash veer singh
Answer Posted / uttam kumar sarkar
Motor pole dipenda upon Speed(N),Frequency(f).
Now we know the Syschronous Speed N=120f/P,
where P is No. of pole,
If synchronous Speed N=1500,
then P=120f/N, where,N=1500rpm,f=50.
P=(120*50)/1500
=4
So the No. of pole will be 4.
thanks to all
Uttam kumar Sarkar
email; engrutm@yahoo.com
| Is This Answer Correct ? | 5 Yes | 2 No |
Post New Answer View All Answers
A jet of fluid strikes a plate What was the force required to counter it?
what is through fault?
What is minimum phase system?
What is different between Difnit time and instatous over current relay
how can you size an automatic voltage regulator?
How to calculate no of Lighning arrestors are required for protecting 50mX 50m*20m cubical building and locations of LA?
What is class ab operation?
If symmetrical fault occurs at the terminal of a synchronous motor then how the motor will act...explain it..
What will be the output voltage of a transformer if it is primarily energized from a square wave voltage source?
Is there any type of starter for DC motor other than two point,Three point and Four point starters?
What will happen if i used 11KV earth ht kit to 11 KV / 11 KV cable termination?
Can clean earth cable be considered as low current cable
why genarator genarating voltage 11 KV?
During Testing of Maintenance Free Earthing, How deep should be the Spikes of Earth Test Meter should be inserted in the soil(one spike is 15 Meter & Other spike is 30 Mtrs away from the Main Earth Electrode. Because, recently, we observed that when spike is inserted 3-4 Inch in the earth- results are better, If spike is inserted 1 feet deep than results are increasing.
whate is the meaning of balance/unbalance,in stabilizers type