why transmission voltages are in multiple of 11kv?
Answer Posted / tom reji
3. The power loss in line is proportional to
resistance and square of current. (i.e. P LOSS=I^2*R).
Higher voltage transmission and distribution thus would
help to minimize line voltage drop in the ratio of
voltages, and the line power loss in the ratio of square of
voltages. For instance, if distribution of power is raised
from 11 kV to 33 kV, the voltage drop would be lower by a
factor 1/3 and the line loss would be lower by a factor
(1/3)^2 i.e., 1/9. Lower voltage transmission and
distribution also calls for bigger size conductor on
account of current handling capacity needed.
4.
| Is This Answer Correct ? | 7 Yes | 18 No |
Post New Answer View All Answers
When we have earthing mesh or underground earthing network in industrial plants, weather we have NT-S or NT-C-S kind of earthing system, so eventually weather we must use 4 or 5 wire in 400 volt level (For example 3×150+70 mm2 or 5×150 mm2) in this connection I would like to know exactly the paragraph of IEC or IEEE number
why ten delta testing is carried out on power transformer
what is the voltages using in movie theaters??? why ??why not other??
distribution is maximum done by a)radial b)network c) parallel d)b & c
What is DTR erection?
Why the output of OP-AMP is always less than Vcc?
How to resolve if Diesel generator stop while running ?
what is relation between ct and pt ratio with multiplication factor of a energy meter? is there any other factor on which multification factor depend?
How to apply 'c' license and also explain what is difference between 'c' and 'b'license.i am also working in one of the private company.i have finished my diploma in 2014 .i have already finished in ITI electrician course.....
Write masons gain formula.
why is the power generator connected as star earthed or star earthed through reactance and what its features ?
I need to connect a synchronous generator to the grid using automatic synchronization and two circuit breakers (one for synchronization, one for end connection to the grid), how to determinate the required diameter of the cables?
Why the dc voltage drop during starting of emergency lube oil pump? The Voltage drop from 135kv to 125 kv for one min. before re-establish to 135kv?
A power transformer 4MVA/11KV/0.415Kv has been out of use in 12years. what maintenance actions/test need to be carried out before energizing.
How to calculate Voltage regulation of 22 KV Over head Line.