ups and invertor battery selection chart and full formula
Answer Posted / thowsif_emerson_csm team
UPS Battery Cacl:-
BATTERY RATING CALCULATION:-
The formula employed rating calculation is as stipulated
below :-
FORMULA EMPLOYED :
DC Current X Duration in Hrs
Capacity of Battery ( AH )=%age capacity utilization
UPS(KVA) x 1000 x Load Power Factor (=1)
Where , DC Current=Inverter efficiency x End Voltage
Hence , VAH = AH x Nominal Voltage
For e.g. : for 3 KVA UPS , 1 hour Backup :
3 x 1000 x 1
DC Current= 17.0 A
0.93 x 10.5 x 18
17.0 x 1.0
Battery ”AH “ = 27.4 AH
0.62
Hence , 18 nos of 12V/28AH batteries will suffice .
TOTAL VAH = 18 x 12 x 28 = 6048 VAH
The following assumptions have been made in the above
calculations :-
1. DC Voltage – 216 for 3 KVA
2. End cell voltage / battery of 10.5 V
3. Load Power Factor = 1.0
4. Inverter efficiency = 93%
% Capacity utilization is :
Duration % Capacity utilization
½ hr (30 mins) 52%
1hrs 62%
2hrs 74%
3hrs 83%
4hr 85%
For ups and invertor battery selection chart lOG On to:-
http://www.sharanapower.com/selection2.htm
| Is This Answer Correct ? | 22 Yes | 10 No |
Post New Answer View All Answers
Name two low frequency oscillators?
1. Why is the speed of shunt motor practically constant? 2. Why dc series motor use to start with heavy loads? 3. advantages & disadvantages of separately excited generator over self excited generator?
Why does an induction generator is preffered as compared to synchronous generator in especially a wind energy power production project?
What is effect of over voltage and under voltage on ACB
Can we transmit digital signal to long distance ?
Who are the manufacturer for Nitrogen based Fire Protectio/explosion prevention for Oil Filled Transformers? India and international both?
placing earthing pit in pathway is correct or wrong??. placing earthing wireGI1/18 inside walls is correct or wrong?. explain!!!
What is the Current equation in series RLC circuits.
what is current check gurd relay?
In electrical what is earth(ground)connection, wht is the importance of it, why it is recomended to maitain below 3VAC between Neutral and earthspecially in PLC used machines?
what is the benefit of floating our DC source? if i have two floating DC source of which 1 has a ref voltage of -21VDC and the other of -18VDC. can it be connected in parallel to share a common ref voltage? if not, how do i make both sources to be of common ref voltage? tks
What are the types of piano switches?
please send me previose rrb junior engineer qustion papers
in a simple IDMT relay we use neutral point of ct for earth fault then what is the requirement of neutral ct and cbct?
Determine a suitable number of slors and conductors per slot for the starter 1 winding of a 3 phase, 3300 V. SO Hz 300 rpm alternator. The diameter is 2.3 m