For an 100kw generator, only 50kw of load is connected.
will the generator generate only 50kw or 100kw. if it
generate 100kw what happens to rest of the 50kw. what
happens if we connect more than 100kw of load?
Answer Posted / bhavesh and rajendra
If we connect 50 KW load to the 100 KW generator at that
time generator will generator 50 kw by restricting its
turbine fuel input and its efficiency will reduce
If we connect more than 100 Kw the frequency of generator
will go down and its power angle will shift to 90 deg and
its operating torque equal to pull out torque and generator
coms out of sysnchonism and it will trip
Is This Answer Correct ? | 19 Yes | 4 No |
Post New Answer View All Answers
What will be advantage if we put some load in neutral of grounded star transformer & loadshortcircuit current,rated current of cable & MCB with example?
what ispositive, negative, zero sequence impedence?
What is CCT (Correlated Color Temperature) ?
what is a synchronizing lamp ?
What is Control & Relay Panel? And Remote Control Center?
HOW CAN WE DECIDE THE SUPPLY VOLTAGE FOR MOTOR ACCORDING TO ITS RATING(IF ANYONE KNOWS GIVE IT WITH EXAMPLE AND ITS CALCULATIONS)
What is the tension required for the 25000 CFM AHU belt
What does the term power factor shows?
What is force on a conductor in a magnetic field ?
Circuit diagram of tube light without starter using electrical choke
what is the terminal voltage of dc series generator running at rated speed at no load?
how can i find ct ratio of meter by seeing name plate of meter and how it should be used in MF calculation if it shows only-/1???
How to checked frequency drive output voltages?
what is the function of gss in the dg set.
How to calculat the ratio of HT\LT in energy meter