what will hapen if secodery circuit is open of current
transformer
Answer Posted / thowsif_emerson_csm team
The CT Will Burn....
Why does opening a CT's secondary cause dangerously high
secondary voltage?
With the flow of both primary and secondary currents the
transformer's exciting current is very low. The secondary
current mmf serves to keep the magnetizing flux in check!
If the secondary now opens the primary current mmf produces
an exciting current 'orders of magnitude' greater than
normal. And, the resultant large increase in flux density
produces an extremely high voltage in the secondary.
Regards,
Thowsif.
Is This Answer Correct ? | 26 Yes | 3 No |
Post New Answer View All Answers
Name the component u would expect to find in a switchgear assembly?
what happens when dc generator coupled with cycle shaft.also explain what happens when its loaded
why the NGR (neutral grounding resistor) always OFF during DG off?
A 10 MVA, 66KV, 50Hz, Y-connected 3-phase alternator has synchronous reactance of 0.635 Ù. It is working at full load at 0.8 lagging p.f. condition. Find torque angle, neglect armature resistance.
is all the servo motors having brake?please specify which servo motors having brake for stop on position and which are not.
what is metering cum synchronizing panel and how it is used?
In a tap changing transformer where is the tap connected, is it connected in the primary side or secondary side?
Who many reason of ignition fail ?
Vibromotor 252MV 1/4HP2P..what is mean by 252MV?
what is the effect of un-synchronized power.
how to store the thunder power?
what happens to the supply voltage if there is any change in frequency?
why Induction Generators are not "Black start" ? and apart from WTGs where this types of generator are generally used?
I am using submission of two ct in one and half scheme for 67/67N protection. Both CTs star point is grounded separately near ct box.Will two point ground give wrong tripping to 67/67N during fault or no matter.
Why is the starting current high in dc motor?