What is difference between earth leakage relay and
restricted earth fault relay ?
Answer Posted / s. malhotra
Restricted EF relay is meant for sensing earth fault/
leakage current in a "restricted zone", a zone bound by the
2 sets of Current transformers - one set at the beginning of
the zone and one at its end.
There is NO particular zone restriction for the normal Earth
leakage relay which will sense an earth fault or earth
leakage downstream of it. Though you may call the entire
downstream as a zone, in comparison to the REF it is left
unqualified
| Is This Answer Correct ? | 23 Yes | 3 No |
Post New Answer View All Answers
i completed my DEEE. and i want to electrical c license. how to get it..?
What is the loss of power of transformer 220kv/33kv,63/80mva of % imp12.05 at 80%load
how to select electrical equipment such as fuse,dg,transformer,motor,msb,wire,cable as per the connecting load..please mention any books to design,take licence
what are the available sizes of pin type terminal lugs in the market today?
why 3 phase is converted into 2 phase using electronics circuit why not 2 phases are diresctly putted from the 3 phase transformer??
Please send 110 kv sb station full single line drawing(sld)
what is the difference between droop mode and ischnorous mode in thermal powerplant?
why we use copper earthing for neutral while for body GI.
What is the Surge for 1.1 Phase Induction Motor(For Eg.1Hp) 2.3 Phase Induction Motor(For Eg.1Hp) 3.AirConditioner(For Eg 1Ton) 4.Refrigerator(For Eg 180Ltr or 160kW) 5.Induction Cooker 4. Ceiling Fan
Why wind turbines wheels rotate constantly
WHAT IS MEANT BY SHEATH VOLTAGE IN 132Kv cable?
how can get electrical "c" licence.i am complited in DEEE.PASSING YEAR OF 1993.WORKING IN PVT COCERN LT LINE.PLEASE ADVISE ME .CELL NO 9994786021
What will be the impact on motor performance if a LT motor is rewound with changed motor winding data as given below:- Original winding data: total 04 wires = 02 wires of 17 SWG + 02 wires of 16.5 SWG. Changed Winding data: total 03 wires of 15.5 SWG wire size Motor rating: 160KW, 740RPM, 415V, ID FAN application. Normal Running Current = 95% of FL Current.
how to calculate the breaking capacity of different breakers.
what is the basic need of domestic loads 1- voltage 2- current