what are the inputs (drawings) we need to prepare loop
schematics??

Answer Posted / rajkumar

starting from your control desk terminal --- i/o details in
i/o cards of ur DCS or PLC ---terminal block details of i/o
rack cabinet----any marshalling cabinets in between that
terminal details---any interface in power room ie.. like
motor control panels---- then field junction box terminal
details---- then final field devices like txr or valve or
motor terminal details. Then you can finish your loop
drawing joining control room /i/o cabinet/marshalling
cabinet/ power interface room if exists/field jn box/field
device terminal.
I hope this will do!
Regards

Is This Answer Correct ?    8 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

NSV type probe stands for

1984


Isometric drawings are generated during _________________ phase of a project

1627


dear sir we have insatlled positioner model no.sipart PS2 make Siemens at our control valves . now problem is if we want to increase the response of valve opening speedy /fast. what parameters do we change for positioner ? any idea. please guide us.

1424


Define the terms Accuracy, precission, Spam, process tolerance while doing calibration of an instrument? Explaini with an example?

1574


what is the process for double acting cylinder pneumatic for 32' v/v

1638






why we are not using the turbine flow meter in the steam service?

1719


why we take %i0.0 as input for twido plc

1672


what is function of switch, and how is it work, explain with difination

1809


Pl send the model question paper of mahagenco account officer post

2265


what is your eligibility criteria for freashers?

1640


How to change dcs card in online. (Dsc is maxdna)

2147


Please any one can provide latest aptitude test,technical test and interview questions for tata consulting engineering (TCE) i need it asap thanks in advance

1564


In my company plc based winders are operated. one day there was a data transmission failure alarm shown on pc. as per sir instruction we have reset master plc but winders were not triped and alarm gone. so what master plc do?

1421


components of control circuit belongs to control valve

1246


where proximity sensor installed on tank in loading arm application

1535