cascade controller is feed back or feed forward or both
Answer Posted / rajkumar
its a feed back loop.
Cascade Control uses the output of the primary controller
to manipulate the setpoint of the secondary controller as if
it were the final control element.
Reasons for cascade control:
* Allow faster secondary controller to handle
disturbances in the secondary loop.
* Allow secondary controller to handle non-linear valve
and other final control element problems.
* Allow operator to directly control secondary loop
during certain modes of operation (such as startup).
Requirements for cascade control:
* Secondary loop process dynamics must be at least four
times as fast as primary loop process dynamics.
* Secondary loop must have influence over the primary loop.
* Secondary loop must be measured and controllable.
Reasons not to use cascade:
* Cost of measurement of secondary variable (assuming it
is not measured for other reasons).
* Additional complexity.
| Is This Answer Correct ? | 18 Yes | 2 No |
Post New Answer View All Answers
How to calibrate an pressure gauge with yantrika test bench?
what should he know if he is an assitent engineer instrumentation in cement industries of experience of 10 - 15 year.
For crude application in floating roof tank, how to calibrate a DP Transmitter? How is the floating roof weight considered?
what is controlling card in dcs? how u measure dcs memory?what is bus in dcs?how u know dcs speed n ehternet speed?
what is loop1 and loop2 in MTS LT?
Please any one can provide latest aptitude test,technical test and interview questions for tata consulting engineering (TCE) i need it asap thanks in advance
HI, can anybody give details about GAS TREATMENT PLANT CONSTRUCTION,as INSTRUMENTATION ENGINEER what are the responsibilites.what are the instruments mainly instrumentation engineer will deal with
why we use cascade control and feed foreword control in 3 element control of boiler drum ?what is feed forward and cascade control system ?
What is the use of GMV in turbine?
how to calculate orifice sizing? and tell me if pipe size bet 50mm t0 200mm then we can use pipe flange??? and above 250mm pipe size should i use D & D/2 Flange? is it right or wrong?
A DP transmitter is used to measure the level of an open tank. The drain line of the tank is connected to a control valve, and is configured as, if the level of the tank is 90% the valve should get open 10%. And if the tank level is 10%, the valve should get open 90%. Draw wiring diagram and explain how to configure DP transmitter and control valve using HART communicator. If the span error at output is 1%, what will be the %opening of the control valve at 60% level of the tank?
Hi,can anyone help me out with PhD programs related to Instrumentation field?I have a degree in electronic Instrumentation?
Boolean algebra
what is zero and span ?
I faced several time siemens ps2 positioner automatically getting Chang in it's set point direction after auto calibration So is there any causes biside this or any permissives ?