Answer Posted / nidal rafeeque
Specifically, these curves denotes the instantenous
tripping current, if fault current crosses the designated
mark.
B : 2-5 times the rated current.
C: 5-10 " " " "
D : 10-15 " " " "
C- curves type are used for heavy currents in normal
working.(e.g. Heaters, Gyesers, Irons)
D-curves types are used for heavy inrush currents.(Motors
etc)
| Is This Answer Correct ? | 50 Yes | 7 No |
Post New Answer View All Answers
what will happen if earth of 33 kv cable (earthed system) is not connected to earthing pit?
what is size of 3phase 4wire cable to be used for 11 ton ductable A.C and how to calculate cable size for different load
how current is reverse from its normal direction during the fault?
In Power cable specification what is U0/U and Um.
EHV current carrying parts need to have smooth finish,then how can a 245kv GIS with emery finish can run so long?
what is the disadvantages of common earthing for AC and DC equipment? (i am talking about inverter control room and inverter duty transformer earthing is common...?)
Explain the working of any one cutting machine
How to select cable the size, what is the parameters use and what is the formulas use for this cable size calculation?
What is s-domain and its significance?
Is it acceptable of installing an earth pit in planters area where bare copper cable, earth rod and connection are susceptible to corrosion due to water?
How 3 phase invertor works?
If I want to connect a capacitor bank on the HT side of a 11kV/415V, 3 phase delta-star distribution transformer to supply Reactive power to it..what practical specifications of a Capacitor bank that can i've??please reply..
How can I calculate per unit (KWH) fuel (Gas/ Diesel both) consumption 1MW unit?
An ISP is granted a block of addresses starting with 150.80.0.0/16. The ISP wants to distribute these blocks to 2600 customers as follows. a) 200 medium size businesses; each needs 16 addresses b) 400 small businesses; each needs 8 addresses c) 2000 households; each needs 4 addresses Design the subblocks and give the slash notation for each subblock. Find out how many addresses are still available after these allocations.
If the feeder rating is 7.5 kw or 10 HP star-delta feeder, MCCB is taken as 63 a, contactors-32 a, how much will be the OLR rating or which range OLR should be considered when we concern about type-2 coordination?