Can someone give a detailed chart on the temperature ranges
which can be measured by various temperature sensors.
Answer Posted / rajkumar
Thermocouple
Type Useful/General
Application Range Notes
B 1370-1700°C
(2500-3100°F) Easily contaminated, require protection.
C* 1650-2315°C
(3000-4200°F) No oxidation resistance. Vacuum, hydrogen or
inert atmospheres.
E** 95-900°C
(200-1650°F) Highest output of base metal thermocouples.
Not subject to corrosion at cryogenic temperatures.
J 95-760°C
(200-1400°F) Reducing atmosphere recommended. Iron leg
subject to oxidation at elevated temperatures--use larger
gauge to compensate.
K** 95-1260°C
(200-2300°F) Well suited for oxidizing atmospheres.
N 650-1260°C
(1200-2300°F) For general use, better resistance to
oxidation and sulfur than Type K.
R 870-1450°C
(1600-2640°F) Oxidizing atmosphere recommended. Easily
contaminated, require protection.
S 980-1450°C
(1800-2640°F) Laboratory standard, highly reproducible.
Easily contaminated, require protection.
T** -200-350°C
(-330-660°F) Most stable at cryogenic temperatures ranges.
Excellent in oxidizing and reducing atmospheres within
temperature range.
RTD Resistance Wire Comparisons
Element Metal Temperature Range Benefits Base
Resistance TCR (Ω/Ω/°C)
Platinum -260 to 850°C
(-436 to 1562°F) Best stability, good linearity 100 Ω at
0°C 0.00385 (DIN-IEC-761), 0.003916 (JIS 1604-1981)
Copper -100 to 260°C
(-148 to 500°F) Best linearity 10 Ω at 25°C 0.00427
Nickel -100 to 260°C
(-148 to 500°F) Low cost, High Sensitivity 120 Ω at 0° C
0.00672
| Is This Answer Correct ? | 4 Yes | 1 No |
Post New Answer View All Answers
Which is your favourite subject & explain any one topic of it.
Linear amplifier.
1. For Steam drum level signal, why do we compensate with drum pressure signal? 2.For main steam Flow signal is comensated with main steam temperature signal and main steam pressure signal why?
How can we use feedback signal frm rtd for monitoring and in dcs for controlling ,then which type of rtd is sutaible 2 , 3,4wire and why ?
Q- What are the application in which PNP transistor is preferred over NPN ?
Please can anybody help for control valve sizing step by step procedure?
how to calibrate mass flow meter (Coriolis)? Example calibration range: 0 to 2500 kg/hr line size 3" fluid: Etheline glycol (MEG)
hi! i want to know about mpse exam.
how many pulses are required by a ac induction servo motor of 4 poles with 50 Hz frequency to rotate by 1 degree?
Which are all the commonly used Bordon tubes in the pressure gauges. Do any one use ASTM A 312 tubes for this purpose?
Can anyone convert a 5/2 way or 3/2 way valve into an ISO valve?
all types of liquid analyzer principle with drawing?
what is KV and XV valve
while i check zero check for dp flow transmitter some fluctuating came (0 to 458 kg/h) what is the reason?
Why do we floating DC in DC system.