What the capacitor Current formula?, For 1 KVAr how amps
its required? for using the KVAr for boosting the PF Design
Calculation.( Eg: for 30 KVAr required how many KW?)
Answer Posted / arnie
For correcting PF KVAr is introduced, thus formula
pf=cos A is significant
there you should have a desired PF. If for example you need
a power factor of .90 to maintain for a 30kVAR the watts
that would come will be:
A=arccos .90
A= 25.84
WATTs= KVAR/tan 25.84
= 62500 watts approx.
remember that for PF correnction it is the KVAR that is in
need of computation and not the watts so the question would
rather be, how much capacitor kVAR you need to correct the
power factor.
Is This Answer Correct ? | 40 Yes | 24 No |
Post New Answer View All Answers
What is the necessary condition for stability.
can we start slipring motor on star delta like we start induction motor ? if yes where will we connect ?
What is resolver and glass scale in CNC how they work?
which one is more efficient, torq, power & ecnomy with the same frame size AC motor / DC motor?
How much voltage we need to apply in 33kv cable during hipot test of cable
What is the rating of a circuit breaker needed for 300 kv load in 33KV supply line of 33/415 transformer ? Whether 800/1200 amp vaccum circuit breaker can perform for a 33 KV line in input in 415 volt in output of the transformer ?
If any cable burnt how can we identify it burnt by high current of high voltage?
A logic circuit that provides a HIGH output if one input or the other input, but not both, is HIGH, is a(n)?
What is the function of Governor in Hydro Power Station? What is the Function of Lightning Arrestor Voltage Transformer (LAVT)?
what is the relationship between current&voltage in practical purpose ?
Define reserve-generating capacity?
WHAT IS THE SIGNIFICANCE OF VECTOR GROUPS IN TRANSFORMER? WHAT WILL BE EFFECT WHEN PHASE DISPLACEMENT CHANGES IN TRANSFORMER?WHAT IS THE NEED TO BE PHASE SHIFT CHANGE BETWEEN THE PRIMARY AND SECONDARY WINDING
What is the meaning of 40X8X2 busbar dimensions for carring load of 400 Amps
if any house we instaled a 1.5 ton ac and its phase cable of wiring is installed but netrual cable of wiring not instaed. my question is that is neutual of house(for other wiring is capable for ac load or a sepeart neutrual wiring required
What are the advantages and disadvantages of the dc motors?