Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

What is minimum distance between three thermocouples (2oo3)
mounted on same pipe line (20")?
Technically accepted by stright line mounted or circler
mounted?

Answer Posted / rajkumar

120 degrees in the same plane (circular), especially if
there has not been sufficient thermal mixing of the process
at the point of measurement. In this case, the average of
the temps should be used for control (as opposed to the
middle of 3) in addition to any deviation checking used to
detect a failed TC.

If any thermal streaming is occurring, then mounting the TCs
linearily down the pipeline reduces your chances of
measuring it.

Is This Answer Correct ?    3 Yes 3 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

send me HPCL paper

10301


please can any one tell me clearly about pid tuning i am confusing about this .how to tune pid easly?

2247


what is the usage of QDV & VOLUME BOOSTER

2315


What is Cavitation in a control valve?

2063


How can we test a bently nevda 3500/42M accelerometer monitor card by simulating it with test equipment?. what king od of signal (milli volts or volts or or resistance ) we should feed in the terminals of the card?

2460


where are following valves are applicable to install. can any valve be installed any line. globe valve butterfly valve boll valve gate valve

1772


when the instrument tapping on pipe line is located below and transmitter is located above the tapping point for liquid service transmitter, what should we do, is there any additional drain valve is required??

2185


State some of balance principle’ advantages?

1178


is there any digitel grevity meter availaible in the market by which we can measure specific gravity of a battery?

2218


How does temperature bath work? How does coil gets heated only by applying some current?

1823


i am preparing for BARC ,so plz mail me how to prepare for BARC. ALSO IF POSIBLE SOME RELATED QUESTIONS. MY MAIL ID IS khushi_4uall2003@yahoo.co.in

3010


How to calculate P,I&D value in PID controller ?

2141


IS there any effect of vortex in low pressure side of the transmiter after the orific in feed water line? if yes then what is the calculation?

2398


please tell me what is a light up procedure of Cfbc boiler and what it's axuillaries of cfbc boiler?

8669


how to change measuring units from mmwc to cubm/h in rosemount air flow transmitter with hart communicator fluke 744

2393