Answer Posted / mathan
loop checking means ,after installation of instruments we
must check full loop(instrument-junction box-control room)
to ensure that whether the instruments are working properly
or not, and whether is it passing the signal or not,whether
is it receiving the signal or not. before we start the
plant we need to check loop..
during the loop check we give some known input
and check the corresponding output at other side(control
room)..if the output is corresponding to input, the loop is
ok..if not means, something fault inbetween the loop.
for example.if you want to check ON/OFF control
valve,during the loop check,when you give 24v dc from
control room ,the valve must open fully, and when you give
0v dc the valve must close.
| Is This Answer Correct ? | 274 Yes | 10 No |
Post New Answer View All Answers
why we are using drum level control valve air to close?
What are primary elements of measuring pressure?
What is intrinsically safe system?
what is the usage of QDV & VOLUME BOOSTER
how to convert cubic metre per hour to newton cubic metre per hour
How to measure the dust in chimney(spm)?
Decibel.
We are using Rosemount 5400 series Radar Level Transmitters in all types of Sump Applications having oily water hdrocarbon petrochemical nature. What we are facing the problem frequently is that always getting reading frezzed at some value. If we do power recycling , sometimes it is working . then making same freezing problem. If anybody faced before such type of problem and also having solution , Please give the answer.
sir ,iam in dem urgent need of HPCL Paper of Instrumentation Branch plz send me at your earliest convenience at ujjwal_sharma1983@yahoo.com
What is mean by analytical instrumentation?
principle of dead weight tester ?
whatis range of marcury filled tempereture gague
What is the difference between modbus,fieldbus & profibus
what is sliding spool valves?
The company where I am working, their is rosemount 5400 series radar type level transmitter, it is meant to show level of filled tank, but along with the level it is showing temperature also, so my question is how a onon-contact type radar type level transmitter can show temperature even if it does not have any contact with the fluid?