We have 2 no. 4MW DG set. and GEB supply.
But, we running, only 1 DG set. when we done APFC/Power
factor setting : 0.90, then winding temp. Low. but when
setting done : 0.83, then Winding temp. increase.
WHY Why ? ? ?, plz give me answer.
Answer Posted / gurucharan singh
this is clear that at lower pf settings, its the DG which
compensate for the KVAR. which results in the high winding
temperature. For this check the plant loads connected. And
KVAR supplied by EB & DG. Also during parallel with grid DG
generally act as KVAR compensator along with KW supplied.
| Is This Answer Correct ? | 2 Yes | 1 No |
Post New Answer View All Answers
how to define tell me about self
am commissioning the trafo without connecting the neutral therefore unbalance will occur what is the alternative solution for this?
Explain Creepage Distance of Insulator
working principle of AC Servo Motor with its construction
What is resolver and glass scale in CNC how they work?
Please clarify 1. Icw: rated short circuit working withstand capacity 2. Icu: Rated ultimate breaking capacity 3. Ics: Rated service short circut withstand capacity 4. other specification of ACB
mention hazard experienced during installation
What is the best thing to protect the motor from running over full current. CT or O/L or pressure transducer at the given pressure rating
Why open circuit test of transformers is conducted at rated voltage??Why not any other voltage??
What are the temperature elements?
what is a reactive power? what is the relation with power factor?
Define thermal resistance in the context of power amplifier.
what is the purpose of slope in the differential relay?why we are using two slope?but in busbar differential we are using only one slope.why?
A 3-phase IM is supplied from 50 Hz system. It runs at speed of 1440 rpm and slip equal to 4 %. Calculate number of pole pairs. A 1 B 6 C 2 D 3
i am an maintenance engineer. one distribution board have 5 feeder. recently its ELR trips frequently, but it take some times after trip( 10min,20min..)but 3 feeder no load. two feeder only loaded. i checked one feeder IR value all values are above 50Mohm.but B phase to Earth is only 9Mohm.any problem about low value