We have 2 no. 4MW DG set. and GEB supply.
But, we running, only 1 DG set. when we done APFC/Power
factor setting : 0.90, then winding temp. Low. but when
setting done : 0.83, then Winding temp. increase.
WHY Why ? ? ?, plz give me answer.
Answer Posted / gurucharan singh
this is clear that at lower pf settings, its the DG which
compensate for the KVAR. which results in the high winding
temperature. For this check the plant loads connected. And
KVAR supplied by EB & DG. Also during parallel with grid DG
generally act as KVAR compensator along with KW supplied.
| Is This Answer Correct ? | 2 Yes | 1 No |
Post New Answer View All Answers
How to calculate the Harmonics losses in terms of cost/unit.
What is the BS(British Standard)code for 11kv motor
When color of silica gel will gets change from blue to pink from Top to bottom?
List few applications of d.c series motor?
What is meant by bus bar protection?
How we can calculate the consumption in kwh of motor on basis of kw @100% load, @50% load & @ no load.
What are your personal skills and abilities for such a Master Course and your possible preparation to undertake this course?
Name a govt approved university which have 100% online engineering course.
Single line diagrams for star to delta and DOL starters.
What are the Return ( Monthly / quarterly/ Annual submitted to Electical Inspector for an establishment (Factory in Maharashtra-- Small scale category having seperate HT line of 22KV ) as per Maharashtra Electricity Act
wat is the first thing dat is needed, 2 lay a cable in some area??
how to store the thunder power?
why ten delta testing is carried out on power transformer
What is the loss of power of transformer 220kv/33kv,63/80mva of % imp12.05 at 80%load
what is the difference between 4pole & 6pole DC Motors & give advantage ?