For a Potential Transformer(PT), the primary neutral
terminal must be grounded before energization. Why....?
What will be heppend if we energize the PT without grounded
the primary neutral point? Why..........?
Answer Posted / om s.
while connecting pt each primary phase winding is connected to phase to earth. The neutral point of load is connected to neutral point of secondary’s. Neutral point of primary is solidly earthed.
If primary neutral is not earthed the zero sequence component of voltages (due to earth fault) cannot flow through primary windings. Hence phase to earth voltages of system which contain zero sequence component do not get truly transformed and measured voltage are distorted. Hence the earth fault on system cannot be sensed on secondary side of VT.
| Is This Answer Correct ? | 22 Yes | 2 No |
Post New Answer View All Answers
The power factor of the fixed load is 0.8, now the p.f is varying from 0.8 to 0.5.
how calculate the electrical load for industry and office
Briefly describe your ideal job?
What is the lower limit of break-down voltage of converter transformer.
block diagram of 2 ups system connected in parallel mode?
HOW TO CALCULATE AMPs OF CURRENT TRANSFORMER IN HT Panel
how to discharge 3 phase power factor correction capacitors
For the requirement of a furnace of temperature range up to 1200 oC using silicon carbide rods, What is the required rate of transformer needed (please do it with all details)?
Why front mounted CT polarities are always towards breaker?
please give some hindalco placement papers for written exam
what is is the potential diffrence between two phase ?
what is lrs tank water resistance.
What is maximum power transfer theorem?
how do you test tachos and servos
clarify types of motor operated valves and advantages