can any one help me?
1.what is corona extinction voltage&corona inception
volatage
2.what is mean by CFVV?
Answer Posted / yasser
Corona Inception
Corona inception voltage is the lowest voltage at which
continuous corona of specified
pulse amplitude occurs as the applied voltage is gradually
increased. Corona inception
voltage decreases as the frequency of the applied voltage
increases.
Corona can occur in applications as low as 300V.
Corona Extinction
Corona extinction voltage is the highest voltage at which
continuous corona of specified
pulse amplitude no longer occurs as the applied voltage is
gradually decreased from above
the corona inception value. Thus, once corona starts, the
voltage must be decreased to get
it to stop.
CFVV - constant flux voltage variation
The short notation of tapping range and tapping steps
indicates the variation range of the
ratio of the transformer. But the assigned values of tapping
quantities are not fully defined by
this alone. Additional information is necessary. This can be
given either in tabular form with
tapping power, tapping voltage and tapping current for each
tapping, or as text, indicating
'category of voltage variation' and possible limitations of
the range within which the tappings
are 'full-power tappings'.
Thus CFVV is defined as the tapping voltage in any untapped
winding is constant from tapping to tapping. The tapping
voltages in the tapped winding are proportional to the
tapping factors.
| Is This Answer Correct ? | 7 Yes | 1 No |
Post New Answer View All Answers
What are the types of class b amplifier?
Can RCD's used to protect the VVVF drive if not why.
Define open loop control system.
can i use 4 number of circuit breaker as single phase manual change over switch? if yes then how plz also send ckt diagram at nazimzamurad@gmail.com
impliment (AB)`+C to transistor representation
What are the advantages and disadvantages of closed-loop control system?
Define liftable weight of a transformer? Does the total weight of transformer include oil weight?
What will be the voltage regulation of a full load and 0.80 power factor lagging load transformer when a two winding single phase transformer has a voltage regulation of 4.5% at full load and unity power factor?
PLEASE TELL ME ABOUT QUESTION PAPER OF UPCL ENTERENCE EXAM.
what is earth pit , how we can measured it, what earth rods reference
how to convert lv line to hv line and viseversa, any losses will occur during this process
why we are not giving the zone 1 trip command to the master trip relay
Maintenance of transformer???
what is the difference between oil surge relay and buchholz relay.
what is the differencce inn series and cascade connection??