WHICH INSTRUMENT USED TO CALIBRATE CONTROL VALVE?
Answer Posted / chek mohidein
For the calibration of a control valve a loop calibrator or
a pressure calibrator can be used between 3-15psi.Check the
valve position for 3psi which is to be 0 for a NC type
valves.In such manner check the valve positon for various
ranges(6psi,9psi,12psi & 15psi).the valve positon shoul be
0 for 3psi and 50% for 9 psi and completely opened for
15psi.
The same procedure is applicable for NO type valves.The
valve is open for 3 psi and completely closed for 15psi.
Any errors occured may be rectified by Zero span adjustment.
Is This Answer Correct ? | 50 Yes | 3 No |
Post New Answer View All Answers
what is commisioning procedure,2)what is is the main work in commisioning in the field tx to dcs, plz send me detail
What are the type of bonnets in the control valves?
what is the advantage of submersible level transmitter compare to ultrasonic level transmitter?
why we are using drum level control valve air to close?
What is the minimum rating availalbe for weld neck orifice in market?
In my company plc based winders are operated. one day there was a data transmission failure alarm shown on pc. as per sir instruction we have reset master plc but winders were not triped and alarm gone. so what master plc do?
why we are using digital signals for I/O & how to measure this signals is getting or not ?
Why grounding is necessary? Give example with diagram.
Which type of diaphragm use in costic line, dm water line, natural gas line, oil line?
What is instrumentation measurement?
Why use ball valves on Gas pipelines instead of gate & or globe valves...means basic diffrence or use of these valves..how designers knows this type of valve with rating is required...
What is PDS and PDMS ?
can anyone guide me how to get any of the previous year GAIL question papers? are they available? 0n 2nd august i have to take the written test.
what is the difference between profibus and controlnet networking.
when the instrument tapping on pipe line is located below and transmitter is located above the tapping point for liquid service transmitter, what should we do, is there any additional drain valve is required??