WHICH INSTRUMENT USED TO CALIBRATE CONTROL VALVE?

Answer Posted / chek mohidein

For the calibration of a control valve a loop calibrator or
a pressure calibrator can be used between 3-15psi.Check the
valve position for 3psi which is to be 0 for a NC type
valves.In such manner check the valve positon for various
ranges(6psi,9psi,12psi & 15psi).the valve positon shoul be
0 for 3psi and 50% for 9 psi and completely opened for
15psi.
The same procedure is applicable for NO type valves.The
valve is open for 3 psi and completely closed for 15psi.
Any errors occured may be rectified by Zero span adjustment.

Is This Answer Correct ?    50 Yes 3 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is commisioning procedure,2)what is is the main work in commisioning in the field tx to dcs, plz send me detail

1864


What are the type of bonnets in the control valves?

1428


what is the advantage of submersible level transmitter compare to ultrasonic level transmitter?

1637


why we are using drum level control valve air to close?

1611


What is the minimum rating availalbe for weld neck orifice in market?

1561






In my company plc based winders are operated. one day there was a data transmission failure alarm shown on pc. as per sir instruction we have reset master plc but winders were not triped and alarm gone. so what master plc do?

1415


why we are using digital signals for I/O & how to measure this signals is getting or not ?

1549


Why grounding is necessary? Give example with diagram.

1759


Which type of diaphragm use in costic line, dm water line, natural gas line, oil line?

707


What is instrumentation measurement?

631


Why use ball valves on Gas pipelines instead of gate & or globe valves...means basic diffrence or use of these valves..how designers knows this type of valve with rating is required...

1838


What is PDS and PDMS ?

1703


can anyone guide me how to get any of the previous year GAIL question papers? are they available? 0n 2nd august i have to take the written test.

1467


what is the difference between profibus and controlnet networking.

2593


when the instrument tapping on pipe line is located below and transmitter is located above the tapping point for liquid service transmitter, what should we do, is there any additional drain valve is required??

1719