WHICH INSTRUMENT USED TO CALIBRATE CONTROL VALVE?
Answer Posted / chek mohidein
For the calibration of a control valve a loop calibrator or
a pressure calibrator can be used between 3-15psi.Check the
valve position for 3psi which is to be 0 for a NC type
valves.In such manner check the valve positon for various
ranges(6psi,9psi,12psi & 15psi).the valve positon shoul be
0 for 3psi and 50% for 9 psi and completely opened for
15psi.
The same procedure is applicable for NO type valves.The
valve is open for 3 psi and completely closed for 15psi.
Any errors occured may be rectified by Zero span adjustment.
| Is This Answer Correct ? | 50 Yes | 3 No |
Post New Answer View All Answers
What is wet leg condition and why is it used?
Why not come out analog output in ABB EL3020 when display show correct value
our kks tagging is crossing more than 12 character please suggest how to take tags in the DCS
hi sir yhis is zahid ali i am preparing for the jspl at oct.4.please send me the recently updated sample paper.
䑰ҕ䔈ҕ䖠ҕ䘰ҕ䛀ҕ䝐ҕ䟐ҕ䢐ҕ䥐ҕŹ
How can you add value to this Industry if offered the job?
What is shielding effect?
can anyone guide me how to get any of the previous year GAIL question papers? are they available? 0n 2nd august i have to take the written test.
how to commission furnace ( water heater)
Which type of diaphragm use in costic line, dm water line, natural gas line, oil line?
What is difference between differential pressure & delta pressure?
we are using centum vp as monitoring with Dell precision work station T3600 but some times PC(s) are restarted automatically . how we can solve this problem? thanks
how the arrangement of equipments done in control room
a flow transmitter [range-0-400mbar] connected in process line. please explain me how to calibrate the flow transmitter , & how to do static error
Can anybody please let me know Orifice plate sizing calculation formula and step by step procedure