Answer Posted / sharafuddeen
we are applying 1000v for LV cables and 2500-5000 volts for
MV cables.the megger value depends on the leakage current
during the injection of voltage.
so for minimum ,if we consider the allowable leakage
current as 100 micro amperes,the minmum insualtion
resistance for Lv cables is 10 mega ohms and and for mv
cables 25-50 mega ohms.
but normally the megger values are in the range of giga
ohms.
the formula KV+1 is not suitable for cables .it is suitable
mainly for the equipments like tranformers,motos...
| Is This Answer Correct ? | 49 Yes | 11 No |
Post New Answer View All Answers
i installed 100kva ups. what KVA genset they should provid in input side? plz any update formula or ans with reason.
How to test REF relay testing for LV panel as per Kahramaa standard?
TCS IS IT COMPANY THEN WHY DO THEY NEED ELECTRICAL &ELECTRONICS ENGINEERS?
What is the current carrying capacity of 0SWG,3SWG,10 & 12 SWG solid bare overhead copper conductors?
working function importance of mdc meter
if you are in a software company,then why do you want to come in a core company like sail, ntpc(where lots of trouble like tension but you have a good life in a it company) ?
How to know any size of cable if there are not written on cable? Answer must be theurical not by experience.
Is it acceptable of installing an earth pit in planters area where bare copper cable, earth rod and connection are susceptible to corrosion due to water?
List the time domain specifications.
What is miller crystal oscillator? Explain its operation?
Why 1/3 is used in symmetrical components?
what is maxemo work permit procedure
I have 1500/1A CT If i connect this CT in 6.6KV bus bar means what will be the voltage present in CT?
how a flip flop can be used as a latch?
why genarator genarating voltage 11 KV?