What core magnetic balance test of transformer?
How to do this test in a three phase Star delta (star-LV,
Delta-HV) transformer?
How to measure and where to measure?
thanks and regards
Austin
Answer Posted / rajukumar sripelli
HI ,
this is rajukumar sripelli from REPUTED TRANSFORMER
MANUFACTURING COMPANY ..testing department ..
AS u all above is not fully correct....
Magnetic balance test is done on TRANSFORMER to see whether
the transformer core is magnetically balanced or
not...AND ALSO WINDING CONDITION....IN FAULT CONDITION DUE
TO HIGH CURRENTS WINDING MAY BE DAMAGE....
for example
we r having delta HV and star winding LV side ...
HV SIDE WE WIL BE HAVING THREE BUSHINGS....THOSE R 1U,1V,1W..
HV SIDE WE WIL BE HAVING FOUR BUSHINGS.....2U,2V,2W,2N...
WE CAN DO THIS MBT (MAGNETIC BALANCE TEST)WITH 1PHASE
SUPPLY(1PHASE AND NEUTRAL(230V)) OR WITH 2-PHASE
SUPPLY(2-PHASES(440V))
1ST STEP OF MBT: GIVE POWER SUPPLY 1-PHASE OR 2 PHASE
BETWEEN 1U AND 1V ,MEASURE THE VOLTAGES BETWEEN 1V-1W AND
1U-1W AND ALSO 2U-2N,2V-2N,2W-2N..
SO HERE IF THE CORE IS CORRECTLY BALANCED THEN WE WILL GET
RESULTS AS FOLLOWS
1U-1V 1V-1W 1U-1W 2U-2N 2V-2N 2W-2N
440 300 140 90 50 40
THAT MEANS HV SIDE : 1U-1V = 1V-1W + 1U-1W
I.E 440V = 300 + 140
AND ALSO LV SIDE : 2U-2N = 2V-2N + 2W-2N
90 = 50 + 40
STEP 2: AFTER DOING THIS ..INTERCHANGE THE CONNECTIONS
BETWEEN 1V-1W AND MEASURE THE VALUES AS ABOVE...
STEP 3: AFTER DOING THIS ..INTER CHANGE THE CONNECTIONS
BETWEEN 1U-1W AND MEASURE THE VALUES AS ABOVE...
IF ANY FAULT IS THERE IN TRANSFORMER WE CAN NOT FIND GOOD
RESULTS....
IF THE WINDING IS DAMAGED .... WE WILL GET ZERO VALUES ....
ex: HV SIDE 1U-1V = 1V-1W + 1U-1W
440V = 440 + 0
AND ALSO LV SIDE : 2U-2N = 2V-2N + 2W-2N
90 = 90 + 0
THIS IS THE ACTUAL APPLICATION OF MANGNETICA BALANCE TEST...
THANKS....
| Is This Answer Correct ? | 287 Yes | 9 No |
Post New Answer View All Answers
Earth has zero potential then what would be the neutral potential ?
how to revers the direction of single phase motor
What does bode plots shows?
What is UPS and How do you maintain the UPS Maintenance? Brief Description on UPS maintenance.
What is the RME and explain the full form and what is the RME work?
WHat is the requirement of installing FAST ACTING EARTH SWITCH in GIS and how is that integrated with protection system. How and when does it operate?
How to decide and select the different earthing wire size for the different types of earthing
what shall be no load voltage of 132/33 kV transformer ? is it 33 kv of 34.5 kV
What is the difference between Droop vs Isoch Control?
What is the difference between the impedance percent and impedance voltage ?
hi friends this is a newcomer in your community of enthusiastic peoples. i am preparing for SSC (CPWD JUNIOE ENGG EXAM FOR ELECTRICAL) pls guide me on the same how to crack it? PLS LET ME KNOW IS ANYONE THERE WHO PASED IT? CAN I GET THE QUESTION PAPERS OF PREVIOUS EXAMINATIONS?
EXPLAIN THE TRANSFORMER MAINTENANCE?
What are the special cables required for explosion proof wiring?
What do you mean by distribution transformers?
How to perform a DC resistance test In Alternator and their proceduces?