Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

how many amps in 1 KVA? V=440v, PF=0.8 and FREQ=50Hz

Answer Posted / guest

if it is 3 phase
KVA=1.732*V*A
1000=1.732*440*A
A=1.31A

for 1 phase
KVA=V*A
1000=440*A
A=2.27A

Is This Answer Correct ?    57 Yes 14 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is limitedly stable system?

1080


Is a direct shorth ciruit on a branch MCCB in a Low Voltage Switchboard a correct means of tesing the performance for discrimination?

2313


What are merits & De-merits of State-Space Method? What is series programming, parallel programming, general programming & direct programming ? And, difference between these programmings Techniques ?

2379


Electrical Engineering

2025


Draw the circuit of clapp oscillator?

1096


How can we increase the capacity of Energy.?

2247


What is slope...? Explain slope 1 and slope 2...?

1572


Why slip ring ind. motor power consumption is low compare to induction motor .same 90 kw motor used same load output

1795


what is the reason for indication of light in the earth lamps of main switchboard.if there is an earth why does one lamp get dim and the other two bright.

2318


What will be in Mahagenco Trade Test Exam? I want to know the same.

3664


i have a 4 Mva transformer 34.5 kv / 480-277 v and i used 2 parallel 3200 amp bus duct for the secondary feeder using 3 ply of bus bar ( 3/8" x 5" ) as a common where the flexible link terminated and 6300 amps breaker for the main, the lower bus duct reaches 70 degrees and the upper bus duct reaches 55 degrees when i used thermal scanner. why the temperature is not balance when the load reaches 3600 amps.

1889


dear all i am kumara now current working in electrical designing of control and relay panel i want learn some substaion design then any book are available. pls mention name and authour

1919


what is the maximum permissible limit value of leakage current and leakage counter reading to replace lightining arrester?

5092


what parameters should we check to reduce the power bill

2301


We have a distribution transformer of 750KVA/11kv/440v and an AVR (Servo Stabilizer) of 750KVA on the LT side of distribution transformer. Also we have an ACB of 1200A on the output of distribution transformer (that is on the input of AVR). We want to have an MCCB on the output of AVR. What should be the rating?

2066