Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

what is the difference between earthed and unearthed cable?

Answer Posted / e.k rajan nair

In 3phase earthed system, phase to earth voltage is
1.732times less than phase to phase voltage. therefore
voltage stress on cable to armor is 1.732times less than
votage stress between conductor to conductor. whre as in
unearthed system, (if system neutral is not grounded)
pahse to ground voltage can be equal to phase to phase
voltage. in such case the insulation level of conductor to
armor should be equal to insulation level of conductor to
conductor. as a thump rul we can 6.6KV UE cable is equal to
11k earthed cable ie 6.6/6.6kv UN cable can be used for
6.6/11kv earthed system. because each core of cable have
the insulation level to withstand 6.6kv so between core to
core insulation level will be 6.6kv+6.6kv = 11kv

Is This Answer Correct ?    26 Yes 6 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

why we need to us lenz's law for synchornous motor

2572


How to calculate the multiplying factor for energy meter with ct ratio given

2028


Why IR value of the (HT cable Plus synchronous motor) is less while individually having IR values in GΩ?

1803


why don't we use the generator as a motor? and what will happen?

1892


Anybody know how schematic diagram for reverse power relay? RPR for generator protection

2139


What are the classifications of oscillators?

1084


diameter of cable and core is doubled then the value of capacitance is

4299


what is the formula for calculating the phase clerance between two phases and phase to earth how to calculate the cable for a motor

2022


what is is the potential diffrence between two phase ?

6431


I have doubt that the supply HZ (very low or high than rated ) may affect the power factor. is it true. ?

1670


how is the cable tray designed & how its total length is calculated for an Industrial plant Say for Ex. (500KW Motor Load)

1898


What will be in Mahagenco Trade Test Exam? I want to know the same.

3697


what is invertor supply and raw powersupply

2111


What are m circles?

1111


what is the effect of power factor of machines in starting current

2056