what is the difference between earthed and unearthed cable?
Answer Posted / e.k rajan nair
In 3phase earthed system, phase to earth voltage is
1.732times less than phase to phase voltage. therefore
voltage stress on cable to armor is 1.732times less than
votage stress between conductor to conductor. whre as in
unearthed system, (if system neutral is not grounded)
pahse to ground voltage can be equal to phase to phase
voltage. in such case the insulation level of conductor to
armor should be equal to insulation level of conductor to
conductor. as a thump rul we can 6.6KV UE cable is equal to
11k earthed cable ie 6.6/6.6kv UN cable can be used for
6.6/11kv earthed system. because each core of cable have
the insulation level to withstand 6.6kv so between core to
core insulation level will be 6.6kv+6.6kv = 11kv
Is This Answer Correct ? | 26 Yes | 6 No |
Post New Answer View All Answers
The advantages of Magnetic flux leakage technique over Ultrasonic technique for non distructive testing of material.
WHY CBCT USE ONLY IN Y PHASE NOT OTHER PHASES
which protection used in power plant?
Name the test signals used in control system
Scott connection is used for A 3-phase to 2-phase conversion B to achieve higher effciency C to save copper D to reduce harmonics
what is a pulse transformer? how rise time of pulse changes when ever the voltage changes?
Why we use ups battery and dsdb battery in thermal power plant
Why PT voltages are measured with respect to ground? What do u mean by voltage or current polarized.
what are factors comes under relay setting (distance relay 7sa52) under OPEN DELTA VTs connection??
WHAT IS START TO INDUCTION MOTER IN STAR TO DELTA OF >5HP ?
What is transmittance?
Please nybody say, weather the result of Bharat Oman is declared or not? Probable date of declare???????
how does directional relay work incase of ac ?
Define sensitivity?
What is the importance of counter based plan & how is it scheduled?