Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

what is the difference between venturi and orifice meters?

Answer Posted / karthik

1. The orifice plate can easily be changed to accomodate
widely different flow rates, whereas the throat diameter of
a venturi is fixed, so that its range of flow rates is
circumscribed by the practical limits of Dp.
2. The orifice meter has a large permanent loss of
pressure because of the presence of eddies on the downstream
side of the orifice-plate; the shape of the venturi meter
prevents the formation os these eddies and greatly reduces
the permanent loss.
3. The orifice is cheap and easy to install. The venturi
meter is expensive, as it must be carefully proportioned and
fabricated. A home made orifice is often entirely
satisfactory, whereas a venturi meter is practically always
purchased from an instrument dealer.
4. On the other hand, the head lost in the orifice for
the same conditions as in the venturi is many times greater.
The power lost is proportionally greater, and, when an
orifice is inserted in a line carrying fluid continuously
over long periods of time, the cost of the power may be out
of all proportion to the saving in first cost. Orifices are
therefore best used for testing purposes or other cases
where the power lost is not a factor, as in steam lines.
5. However, in spite of considerations of power loss,
orifices are widely used, partly because of their greater
flexibility, because installing a new orifice plate with a
different opening is a simpler matter. The venturi meter can
not be so altered. Venturi meters are used only for
permanent installations.
6. It should be noted that for a given pipe diameter and
a given diameter of orifice opening or venturi throat, the
reading of the venturi meter for a given velocity is to the
reading of the orifice as (0.61/0.98)2, or 1:2.58.(i.e.
orifice meter will show higher manometer reading for a given
velocity than venturi meter).

Is This Answer Correct ?    170 Yes 28 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Sir, I am working as a Instrument Engineer in Grasim Industries. Can any body provide question answer for interview purpose

2340


Why rdt and thermocouple both give different output .and one things more, how to generate  ohm or mili volt  plz mail me merajalam143545@yahoo.com

2849


TECHNICAL/ARTITUDE

2298


How to calibrate H2s Dectector

1674


How to convert mmWc(mili meter water colam) to tph(ton per hour)?

1044


how can i calibrate the temperatuture gauge used by temperature bath(dry block) i mean step by step procedure?

1719


we are having yokogawa centum cs3000 dcs in our power plant. i need some of the operator guides NOT to appear in HIS0163 AND HIS 0162 but it shoul appear in HIS0164 HOW TO DO IT?

2641


why we are using magnet for calibration of gas detector?

2289


What is super thermocoupal?

2268


key exchanges in wpa,wpa2,tls

1981


we are using centum vp as monitoring with Dell precision work station T3600 but some times PC(s) are restarted automatically . how we can solve this problem? thanks

2230


What is the difference between PLC and DDC?

2230


To become an Instrument DESIGN engineer, is there any softwares or training to become Instrument Design engineer, plz suggest me, Iam very much interested in designing.

3506


1.what is controller proportional gain 2.what is the controller intergral action time. 3.A proportional plus derivative controller that has a proportional band of 20% and a derivative action time of 0.1 minutes. Construct the shape of the output waveform for the triangular input if the input rises and falls at the rate of 4 units per minute.

2731


Difference between 2-Valve Manifolds, 3-Valve Manifolds and 5-Valve Manifolds 3 with diagram

3151