Why Transformer in KVA?
Answer Posted / krishnendran
kVA is the unit for apparent power. Apparent power consists
of active and reactive power. Active power is the share of
the apparent power which transmits energy from the source
(generator) to the user. Reactive power is the share of the
apparent power which represents a useless oscillation of
energy from the source to the user and back again. It
occurs when on account of some »inertia« in the system
there is a phase shift between voltage and current. This
means that the current does not change polarity synchronous
with the voltage. But the heat generated in a winding as
well as the eddy current losses generated in a transformer
core depend on the current only, regardless of whether it
aligns with the voltage or not. Therefore the heat is
always proportional to the square of the current amplitude,
irrespective of the phase angle (the shift between voltage
and current). So a transformer has to be rated (and
selected) by apparent power.
| Is This Answer Correct ? | 21 Yes | 3 No |
Post New Answer View All Answers
how can we determine size of a cable by knowing the kw or current rating of a load?how can we calculate the resistance box of a slip ring motor?
Can RCD's used to protect the VVVF drive if not why.
Define conversion efficiency of a power amplifier. What is its value for class c power amplifier?
What do you mean by turns ratio of instrument transformer?
How to work definite,over pluxing,revers power,OSR relay
apti mainly on logical reasoning, verbal and non-verbal ability (70 percent) and remaining technical. I was in ee but technical had mech ques like on turbines and welding.
how to calculate the capacitor to maintain power factor?
i need of the bhel question papers along with answers and also give some website names for the downloading question (electrical and electronics engg question)please help me....
why is the power generator connected as star earthed or star earthed through reactance and what its features ?
WHY IS THE EARTH FAULT CURRENT ALWAYS LESS THAN THE NORMAL CURRENT??
how harmonics generated in induction furnance? how minimise it?
11kv/433v delta/star distribution transformer primary side full load Ht current is 83.33A in , but input side VCB rating 800A.why?
Could Please Explain briefly. Why used stabilizing resistance series with High impedance bus differential protection relay.
List the advantages of star-delta starter with induction motor?
What is BusBar integrity test and how it is conducted?