how to calculate the mf of kwh meter,if ct the ratio on
meter is 100/5A
Answer Posted / kishor shetty
MF=(CT ratio)*(PT ratio)if HT side
eg; =(100/5A)*(11000/110V)
=20*100
=2000
in LT side
MF=(CT ratio)
=(100/5A)
=20 (PT is not applicable for LT side)
| Is This Answer Correct ? | 148 Yes | 23 No |
Post New Answer View All Answers
What is non-minimum phase transfer function?
What is the function of RCBO? What are the different sensitivity ratings & each application?
how to measure earth resistance of a substation
A jet of fluid strikes a plate What was the force required to counter it?
what are the major & minor faults that occur in an inverter and in UPS ? And how to repair and resolve them ?
What range of speed can you get with the armature control method of speed control of d.c. Shunt motor?
what is cathodic protection and why it use in industries?
In case of salient pole alternator when number of poles are 4 or more than 4 it helps the flux wave to be sinusoid as air gap length is increased from center to tip , but if the number of poles are 2 how does the flux wave is sinusoidal?
Parts of machine and their discription in details with suitable photo
what is a bus riser in power system and why it is used
Why the cores of large transformers build up of circular cross section?
I have an existing old MCCB. ABB Model SACE, the rating are: Ue = 660 volts, Iu =1250 Amps, 3 poles, Ith (max) =800 amps at 45 deg C. I need a circuit breaker for my 3 phase motors, 380 volts 60 hz. the supplier required the minimum ampacity of the breaker to be 911 amps. can i use this breaker with rating of Iu =1250 amps but Ith = 800amps maximum?
Who many reason of ignition fail ?
WHAT SHOULD BE THE BEST CURRENT RATINGS (PRIMARY / SECONDARY)FOR A CT INSTALLED AT THE INCOMING 11KV PANE? WILL IT BE CALCULATED ON THE BASES OF MAXIMUM DEMANT VALUE OR ON SUM OF ALL TRANSFORMER'S KVA? NOMALLY MAX DEMAND REPRESENT THE MAXIMUM OPERATING LOAD OF THE PLANT AND TOTAL KVA OF (SAY 5 NUMBERS TRANSFORMERS) REPRESENT THE CONNECTED LOAD. WHICH i.e. MAX DEMAND KVA OR CONNECTED KVA ARE BETTER TO USE FOR CT CURRENT CALCULATION? PLEASE ANSWER.
How will polarity test of Dy5 Transformer ?