What is min and max voltage between earth and neutral/phase
if it perfect earthing?
Answer Posted / ravindra sharma
The question can be replied in three conditions
When earthing is perfect and (a) neutral is solidly
earthed at transformer end then the volatge between erath &
neutral is zero and earth and phase is the same as between
earth & neutral in all conditions whether all pahases are
perfect or one of them faulty. and between earth and phase
is the same as neutral and earth i.e. nominal value when
system is healthy
(b) when neutral earthing is not solid but with resistance
then Voltage between neutral and earth will be zero in case
of balanced load on all three phases and it may rise max.
upto a value equal to phase value if there is fault on one
of the phase,depending upon the value of earthing
resistance of the neutral earthing. Value of earth to phase
will be nominal value if system is balanced and healthy,
and may go max upto phase to phase voltage if there is
fault on one of the phases and mind it again value in case
fault will depend on fault resistance.
In nut cell we can say that min. value between neutral and
earth will be zero volt and max. will be nominal voltage
(e.g 230 volt in indian LT supply case) and voltage between
neutral and phase will be nominal voltage is system is
balanced and healthy and mind it in case of fault it may go
down min. to zero value and max to phase to phase voltage!
and that is what great abt electrical enineering.
| Is This Answer Correct ? | 48 Yes | 22 No |
Post New Answer View All Answers
Is there a possibility to use such a treshold voltage for the NMOS part of a CMOS circuit that during the switching it will start conducting only after the PMOS part will be already closed, by this eliminating the leakedge current? Please note, I'm not asking about the well bias in standby mode, but about the "antileakedge" measures during normal operation.
How we can calculate the Amps for the cable Ex:- For 1sqmm wire how many amps we can draw (calculation)
In the magnetic fluxes, what is the role of armature reaction?
why we take movement of rotor always in counter-clockwise direction in 3-phase induction motors?
What is the alternate solution for testing of polarity by using polarity tester while its milli ammeter does not works?
How halogen & merquery lamp works.
in my industry we are using 3 step up transformers for induction heaters..i.e 415/580v and other are 11/440v.in power consumption does a step trnsformer makes any difference compared to step up?? plz explain
can some one clearly explain why -48 volt DC use in telecom site????
How to calculate total harmonic distortion level(THD) in VFD? and how can we reduce harmonics?
Why do we need a separate control desk & PLC control panel in Boiler plant or coal handling plant? Can we provide cost effective Control desk cum PLC panel. Is there is an specific need for control desk.. kindly advice.
explain PV modules in solar energy generation.
What kind of Neutral CT can be placed in 11/0.433KV transformer to be used and what are its specification?
5.WHICH TYPE WELDING PROCESSES USES NON CONSUMABLE ELECTRODE.........
What is the maximum No. of out going mccbs permitted from an LV distribution paqnel? What is the ampere relation between incomer and out going switch gears/mccbs?
please send me the L&T Emb. sys. placement papers and entire details of pattren