What is min and max voltage between earth and neutral/phase
if it perfect earthing?
Answer Posted / ravindra sharma
The question can be replied in three conditions
When earthing is perfect and (a) neutral is solidly
earthed at transformer end then the volatge between erath &
neutral is zero and earth and phase is the same as between
earth & neutral in all conditions whether all pahases are
perfect or one of them faulty. and between earth and phase
is the same as neutral and earth i.e. nominal value when
system is healthy
(b) when neutral earthing is not solid but with resistance
then Voltage between neutral and earth will be zero in case
of balanced load on all three phases and it may rise max.
upto a value equal to phase value if there is fault on one
of the phase,depending upon the value of earthing
resistance of the neutral earthing. Value of earth to phase
will be nominal value if system is balanced and healthy,
and may go max upto phase to phase voltage if there is
fault on one of the phases and mind it again value in case
fault will depend on fault resistance.
In nut cell we can say that min. value between neutral and
earth will be zero volt and max. will be nominal voltage
(e.g 230 volt in indian LT supply case) and voltage between
neutral and phase will be nominal voltage is system is
balanced and healthy and mind it in case of fault it may go
down min. to zero value and max to phase to phase voltage!
and that is what great abt electrical enineering.
| Is This Answer Correct ? | 48 Yes | 22 No |
Post New Answer View All Answers
For overhead protection we use which transformer?
As per standard, transformer body earthing and other Equipment earthing (Equipment earthing) did not connect. but in LT side termination we are doing metal glanding in both side Transformer to PCC Panel through armoured cable, now X'mer body earthing and PCC Pane earthing (Equipment earthing) both are connect.is this safe for X'mer or other equipment?
l&t switch FN 63 handle position can we change
What is difference between slip rings and carbon burushes?
What is the formula formula for Busbar sizing and what are the things to be consider for Busbar Calculation?
Anybody tell me about modbus hex address of l&t trivector meter er300p??I want to read voltage,current,kwh etc via rs485...If anybody have a manual then send on my mail..Brijeshmodi18@gmail.Com
is there any current and voltage drop on liquid resistance starter water/soda tank ?
can i use the six sigma method which is used in management area, in state estimation of power systems?
How cable from Kit-Kat to main switch, from starter to motor are designed?
What is FM200 Gas??Applications........
I need the list of Universities who have summer intake for BS degree in Electrical Engineering.?
How should i design a 1ph & 3 ph transformer. Kindly let meknow all steps and formulaes related to design from scratch.
what is the voltage between earth to neutral in lift.
IF 8255 CONTROL WORD IS 94H,Tell the chip port work mode ?
Define non-touching loop.