what is the difference between earthed system and unearthed
system.. where do we use unearthed system because in
electrical catalogues always cable for earthed and unearthed
system is given..pls elaborate
Answer Posted / bikash chandra pal
WAHT IS EARTHED SYSTEM??
when the source(it may be feeding generator neutral point
or feeding transforme neutral or a bus through a zig-zag
transformer etc)neutral point of a perticular voltage level
of a system is earthed(may be solidly or through a
resistance/inductance), then that perticular voltage level
of the system is called as earthed system.
WAHT IS UNEARTHED SYSTEM??
When the above said neutral point is not earthed then that
perticular voltage level of the system is called as
unearthed system.
ADVANTAGES OF EARTHED SYSTEM
The system eathing(solidly or through a resistance or
impedance) is done to provide a returne path of earth fault
current, which in turne helps
1)To isolate the faulty part of the system due to earth
fault by sensing earth fault current.
2)To Reduce the insulation requirement of phase elements of
equipments connected in that voltage level & cost of the
equipment/s in turn. VIZ: Earthed grade cables are less
costlier than unearthed grade cables.
3)Fenomennon like ARCHING GROUND can be avoided.
So,
System with lesser Equipment cost(refer SL.NO.(2)above),
health of the concern part of the system(Refer sl no.(1) &
(3)above) remain protected.
DISADVANTAGES OF EARTHED SYSTEM
Possibility of interruption of power supply due to earth
fault,is more in EARTHED SYSTEM than UNEARTHED SYSTEM.
ADVANTAGES OF UNEARTHED SYSTEM
1)Possibility of continuation of power supply is more in
UNEARTHED SYSTEM, as tripping of system due to first earth
fault is not happens.
2)sensing of presence of earth fault through sensing of
concern system's neutral displacement is possible & planned
maintenance/earth fault clearence of the system is
possible,which supports better availity of the system &
lesser interruption of process.
DISADVANTAGES OF UNEARTHED SYSTEM
1)Isolation of the faulty part of the system due to earth
fault by sensing earth fault current is not possibele due
to first earth fault.
2)Insulation requirement of phase elements of equipments
connected is higher Hence cost of the equipment/s is
higher. VIZ: unearthed grade cables are costlier than
earthed grade cables.
3)Fenomennon like ARCHING GROUND is there.
So,
Capital investment is higher for unearthed System, But
availability of system is better.
Is This Answer Correct ? | 41 Yes | 1 No |
Post New Answer View All Answers
what are the differant std sizes of cable trenches?
what is the major difference between LIBBP & HIBBP.. which one is most preferable..
Do closed loops systems require manual input?
how many parameters can integrate with fire alarm basically ?
How maesure earth neutral value & how much maximum value value required in between earth & neutral.
how to calculate the distance relay faulty zone?pls explain?
What is the Resposiblity of Electrical Utility Engineer
2. What are the parameters of EHT sub-station?
how to setting voltage RTCC panel
Draw the equivalent circuit of crystal oscillator?
what is ground fault in ACB?
What is an Air COmpressor
234 MVA Generator 3 phase Short circuit current Values required? Gen set Rating-234 MVA, Gen Voltage-18kv, PF;0.8, Xdv:23.5 %, Transformer Rating-18/380KV, 680MVA,Yndd1 two winding, Step up TR, ZT:35.50 %,X/R 4.33 Gen CB Position, CB open ,Disconnected open, Generator Running Voltage 18 Kv, Bi mistakes generator side earth switch Closed during that time short circuit current level in 3 Phase required, and how to test on site 234MVA Generator Short circuit current,
What is the method to solve circuit using source transformation?
Why transformer used in UPS??