What is different between Metering CTs and Protection CTs?
Answer Posted / rk
metering cts are desined not to record fault current i.e.
if ctr is Ex. 200/5 at a fault current of 2000amp the
secondary current would be still 5 amps not 50amp. reverse
is in prot cts it will serve 50amps if its ALF permits .
Metring CT are like acc class 0.5 etc Protn CTs have 5P10,
5P20etc i.e. it will maintain its ratio up to 20times the
the primary current (200amp)of ct.
| Is This Answer Correct ? | 13 Yes | 4 No |
Post New Answer View All Answers
for 5KW resistive load can anyone please suggest me whether to go for UPS/Inverter or Generator depending upon cost calulations
Explain and give examples about VCB?
11kv/433v delta/star distribution transformer primary side full load Ht current is 83.33A in , but input side VCB rating 800A.why?
how to calculate the Neutral transformer impedance?
how i chosse capacitor bank if my energy meter is 48 kvr? tell me capacitor bank chossen formula?
What is mean 2XWY
What are the three major categories of error?
when elecromagnatic waves are propogated in a wave guide?
how to calculate IR value of 33KV cable ??
Which device of PlC does share load between DG sets when DG are running in perallel?
What is the dependency of stiffness on load angle??
How can we choose the rating of submersible motors
What is the type of earth fault protection used in battery? explain.
In our factory so many iron pillors are exists for supporting the shed/Hangar. If do more no of earthings at one piller instead of doing more earth pits in many locations and running earth strip around the hanger, I can save the money. Please suggest this method is acceptable as per Is specifications though the Earth resitance of the farthest piller is with in the limits as per IS specifications.
what will happen when the dc supply is given to the capacitor?