Why Transformer in KVA?

Answer Posted / pankaj rajput

The copper loss of a Transformer depends on current i.e.
I^2 R and the iron loss depends on voltage. Hence the total
losses depends on volt-ampere (VA) and not on phase angle
between voltage & current.

Therefor the losses in a transformer are independent of
power factor which is cosine of angle between voltage &
current.

That's why the rating of transformers is in KVA and not in
kW.

Now coming to Efficiency of a transformer: Yes it depends
on power factor of load. Because the
Efficiency = Output/Input
= (Input - Losses) / Input
= 1 - (Losses / Input)
= 1 - [Losses / (Vs * Is * Cos phi + Losses)]

Efficiency is inverted V curve (Y-scale) and the peak of
curve appears between 50-60% load (X-scale)for various load
power factors. Efficiency increases as the power factor
increases.

Is This Answer Correct ?    23 Yes 6 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Why a Permanent Magnet Generator has higher frequency as compared to frequency of main alternator?

1424


When a square wave is applied to primary of a transformer then what will be output wave form of secondary ?

1588


either water sensor or flow meter,how we observe the water level, f any other equipment are in market ?

1427


What is the method to solve circuit using source transformation?

662


why the value of k is more in shell typr transformers?

1578






Difference between field rheostat and armature rheostat.

699


What are the weight of 800KV DA,DB and DC type tower ?

2710


TYPE'S OF BREKAR ,WHAT IS TRANSFORMAR & SAFTY. STARTER DOL & STAR DELTA STARTER.

2110


How to megger test 11 kV cable and the acceptance IR value

2449


why the voltage and current in a long transmission line are called travelling wave?

1788


what is difference between bus coupler and auto transfer switch

3333


If there is major % of Voltage harmonics in the system, how can it be control or reduced?

1571


what are the values of VRY,VYB,VBR,Vry,Vyb,Vbr,Vrn,Vyn,Vbn for Magenetic balance test of 100 KVA and 63 KVA Distribution transformer

2434


WHY CBCT USE ONLY IN Y PHASE NOT OTHER PHASES

1624


Is there any problem about which the drive (inverter) doesn't show/display the alarm and/or fault but instead of this , it doesn't work ? I want to know that could there be any kind of problem in the drive when the drive doesn't display the alarm and/or fault ?

1518