We have 250 KVAR cacitor bank & our average load is 200kva
but our power factor is average 0.66 how can we maintane
it? how can we balance our load?
Answer Posted / joseph
It is better to express the `Load' in kW. In your case it
is assumed that the average load at a P.F. of 0.66 is about
132 kW. Please note that excessive capacitors in circuit
can act as `Load'. Hence, firstly ascertain whether the
Power Factor is 0.66 lag (lesser capacitors than required)
or 0.66 lead (more capacitors than required). The best way
is to switch off all the capacitors for some time and take
the P.F., kW, KVA readings from your meter. Based on this
suitable solution can be provided.
| Is This Answer Correct ? | 9 Yes | 2 No |
Post New Answer View All Answers
How many types oil using in transformer ? How many letars using in transformer..?
Describe the colour rendering properties of i) tungsten filament lamps ii) tubular fluorescent lamp
A well system is when , no. of bus bar is less or more. Tell me the concept of it.
How cable from Kit-Kat to main switch, from starter to motor are designed?
1- What is the Polarization Index number be good for 15KV 3c#500MCM electrical cable? 2- Can I use the IEEE Std 43-2000 to perfom the PI test? Thanks
What is the difference between security constraint unit commitment and security constraint optimal power flow?
am commissioning the trafo without connecting the neutral therefore unbalance will occur what is the alternative solution for this?
in general it is observed in power stations, the tertiary winding is used in higher rating Y-Y auto transformer but not in Y-Y power transformer. is the tertiary winding is compulsory then why it is not using in power transformerÂ
How to calculate the Efficiency of Chiller
I am getting above 60 V as open delta voltage against single phase unit ICT at tertiary delta formed and ICT getting trippped on NDR. ICT tested and found in order. PTs provided on tertiary are tested and in order. what may be the reason?
is it possible to turn on the single phase star delta on delay timer using 24 v dc ?
What is the function of interposing current transformer?
temp of cast resin 1500kva tx formerwent up to 138.c but came down very fast to about 100.c within 20 mins when load was reduced from 70% to 60%
what is magnetizing current test in power transformer
What is the IS standard for MCCB to be use (As per capacity of AMP)& for ACB also.