Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

what is the minimum dielectric stregth of transformer oil.

Answer Posted / zahid noor

Minimum dielectric strength of transformer oil is a wrong
question itself, For New insulating transformer oil, the
value is 70kv, where as oil in use has values ranging from
25 kv to 50kv , depending upon various factors like ,
running hours of use, impurities, moisture content, sludge
content etc, but it is advisable to discard old oil, if
value does not improve after filteration above 30 KV

Is This Answer Correct ?    74 Yes 14 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Hello to all, Please someone can send me HPCL ELECTRICAL Engg. Sample papers to me? Its urjent....my email address is.... raviasiapacific@gmail.com

2183


how does ELR works? explain

2772


What is the drawback of class b amplifier? How is this minimized?

1179


why can the rotor of 3 phase slip ring induction motor not be a 2 phase rotor?

2107


Please tell me in DETAIL about the following 3 types of fuses or recommend me a good power system protection book or a website link ? 1.Dropout Fuse 2.Striker Fuse 3.Empulsive fuse (not sure if its impulsive or explosion fuse , sorry)

2150


is it true there's a big difference in using Cummins or Denyo...especially power output or leakage

1985


HOW THE OLTC TRANSFORMER SAVE ENERGY IN COMPARISON TO OFF LINE TRANSFORMER AND IS IT ECONOMICAL TO REPLACE THE OFF LINE TRANSFORMER TO OLTC TRANSFORMER

2254


what is accuracy ? in any meters , coils accuracy . how can u defined that ?

2491


Difference between shunt, PMG and AREP excitation. Which is the most reliable between PMG and AREP.

9652


In a 3 phase 4-wire system. For a 3.5 core cable if all loads are single phase and balanced, what will be neutral current? will it be sum of all phase currents? Or it will be zero? And if loads are unbalanced what will be neutral current?

1754


what kinds of Transformer oil grade is better for power transformer ?

1694


What will be the size of copper cable (each for 3 phase and 1 neutral) from Service connection Kit-Kat to Panel Board (i.e. to main switch) for a 6 pole 3-phase AC induction motor of 200 H.P. capacity? Amp-255 A, Frequency:- 1450 rpm.

2011


what is meant by tranformer impedance?

2652


how does the rotating m.m.f is produced in the 3-phase induction motor and how the poles are created in 3-phase induction motor ?

2693


Explain cos(theta) and Sin(theta)

2158