What is the power ratio between power in Star and Delta
circuit?
Answer Posted / baswaraj
The power ratio between Star to Delta is 1:3
Here is the Explanation:
Let?s suppose Vs be the supply voltage per phase.
So the line voltage of the supply will be ?3Vs.
Now assume any type of load; for simplicity assume it a
only resistive load.
And let it be ?R? per phase.
For Delta connected load:
Calculation for per phase power; PD= I2R
Where I ? load current (per phase)
And,
I = ?3Vs/R {as line voltage of the supply is directly
applied to the phase of the delta load}
So,
Pd = (?3Vs/R )2R = 3Vs2/R watts per phase.
For 3 phases:
P3D = 3Pd = 3*3Vs2/R = 9Vs2/R watts.
Now for Star connected load:
PS = I2R = (Vs/R)2R = Vs2/R watts
For 3 phases: P3S = 3PS = 3 Vs2/R watts
Conclusion:
P3S / P3D = 3Vs2/R / 9Vs2/R = 1/.
| Is This Answer Correct ? | 26 Yes | 58 No |
Post New Answer View All Answers
How many types of electric motors are there?
what is allowed value of zero sequence impedancce of 6.6 kv nuetral earthing transformer ?what is the actual value
WHAT IS THE FORMULA FOR CALCULATING CURRENT RATING(DIRECT IN GROUND OR AIR) OF ARMOURED(XLPE) CABLE OF 4C,16Sqmm?
3phase motor can be used as a Prime mover for alternator.
What is the disadventage of gland earthing(power cable) if any. ?
what is the use of sdf?
explain the process of commutation in a dc machine. Explain what are inter-poles and why they are required in a dc machine.
Diagram on interconnectivity of 11kv transformer with RMU (i.e, one incoming and two outgoing or two incoming and one outgoing)
As per standard, transformer body earthing and other Equipment earthing (Equipment earthing) did not connect. but in LT side termination we are doing metal glanding in both side Transformer to PCC Panel through armoured cable, now X'mer body earthing and PCC Pane earthing (Equipment earthing) both are connect.is this safe for X'mer or other equipment?
what is the best method of grounding in 30 MW generator?
The metal-enclosed switchgear and controlgear is subdivided into three types: 1. metal-clad switchgear and controlgear; 2. compartmented switchgear and controlgear 3. cubicle switchgear and controlgear. What is the main differnence between them. State some example.
Explain how you intend to work under pressure to meet up with deadline target?
what is circuit breaker in transfomer and where it used
How could I get a certificate of competency as Electrical Supervisor? I have completed By BTech in Electrical this year(2012) for VJTI Mumbai Maharashtra. Is it compulsory to be produced while joining?
What is the meaning of utility ground and clean ground? How the distribution panel is grounded?