What is the power ratio between power in Star and Delta
circuit?
Answer Posted / baswaraj
The power ratio between Star to Delta is 1:3
Here is the Explanation:
Let?s suppose Vs be the supply voltage per phase.
So the line voltage of the supply will be ?3Vs.
Now assume any type of load; for simplicity assume it a
only resistive load.
And let it be ?R? per phase.
For Delta connected load:
Calculation for per phase power; PD= I2R
Where I ? load current (per phase)
And,
I = ?3Vs/R {as line voltage of the supply is directly
applied to the phase of the delta load}
So,
Pd = (?3Vs/R )2R = 3Vs2/R watts per phase.
For 3 phases:
P3D = 3Pd = 3*3Vs2/R = 9Vs2/R watts.
Now for Star connected load:
PS = I2R = (Vs/R)2R = Vs2/R watts
For 3 phases: P3S = 3PS = 3 Vs2/R watts
Conclusion:
P3S / P3D = 3Vs2/R / 9Vs2/R = 1/.
| Is This Answer Correct ? | 26 Yes | 58 No |
Post New Answer View All Answers
hai iam arunkumar. i have applied for an section enginner in rrb. i want lat 5 years solved question papers. if u have please sedn it to arun30682@gmail.com
What is stacking factor? What is its approximate value?
send me all basic electrical question and answers
What is grid collapse? what is the reason for it?
What is Auto Mains Failure Panel & Auto Synchronizing Panel
cc of scorpio?
Anyone who can recommend an equivalent to Envirotemp FR3 of Cooper?
The Howland current source produces a A Unidirectional floating load current B Bidirectional single-ended load current C Unidirectional single-ended load current D Bidirectional floating load current
what is your aim
which is the most advanced form of SF6 BREAKER?Can we use other gases to quench the arc?
WHY THREE PHESE SYSTEM VOLTAGE APPLIED IN 440 VOLT
What is effect of over voltage and under voltage on ACB
Is it acceptable of installing an earth pit in planters area where bare copper cable, earth rod and connection are susceptible to corrosion due to water?
Do closed loops systems require manual input?
if a.c supply is given to the motor,, what happen?