What is the role of link in neutral in a three phase ac
system?
Answer Posted / nbsubrahmanyam
In 3phase ac system ,In the case of link in neutral, we
should not use fuse.
(neutral is using at distribution level for getting single
phase or 3 phase 3wire 4wire system to supply the power to
the some loads),
Suppose we use the fuse in the neutral line,if any fault
or break occur in the neutral line, but current flows from
phase/line to load and come to neutral wire where it has
break,there will be a chance to shock to human
beings/workers who will do the works regarding the repairs.
we generally putting fuse in phase/line for protecting
the equipment/device from high voltages/currents.if any
fault occur in the phase/line ,current will not flows from
fuse,only it will come fuse hence there is no problem. but
in the case of neutral, the current flows through out
equipment that may lead to creat some problms as mentioned
above.
that's why we w should put only link for neutral in three
phase ac system.
Is This Answer Correct ? | 22 Yes | 4 No |
Post New Answer View All Answers
Why does the adjacent zone of protection overlap?
what is the solution for meger test failed the MV cable?
What is difference between slip rings and carbon burushes?
how to size H.T & L.T Panel ?
What are the difference between normal application Transformer and Solar application Transformer?
For R-L or R-C ckt,time constant formula is L/R and RC respectively and its unit is in sec.Pls tell me the derivation
Why is water motor not taking the pressure? what is the problem?
What is EMC filter in VVVF Drive ?
we have 2.2kw,Y,3000rpm motor but 6leads found in TB what happen if we connect in delta?
why +24 v and -48 v give to BTS? If -48v protect from surge then why we not use -24 v?
sir please send me techinical questions for junior engineer posting in bangalore railway i am diploma holder
Can XLPE/SWB/PVC (P3) 7C X 2.5mm2 be replaced by Can XLPE/SWB/PVC (P2) 7C X 2.5mm2??? P3 vs P2
how many safety really of DG sets.
write down the formula of cable size in RM if current is 50Amp.
what is the difference between skin effect