WHY IS RESTRICTED EARTH FUALT PROTECTION NEEDED?? WHY CANT
DEIFFERENTIAL PROTECTION SUFFICE???
Answer Posted / shipra
restricted earth faukt protn is for unprotected zone of
neutral to earth.
Diffetential protn will work only if the falt is with in
zone of CT so that it can get a differential current. If
there is a fault between neutral CT and earth the fault
will be feeded and no diffential current will be there as
it is balaced through primary side, secndary side & nutral.
| Is This Answer Correct ? | 19 Yes | 32 No |
Post New Answer View All Answers
Draw a circuit diagram in which if button is open we can use socket and bulb as a series test circit and if button is close than simple we can use socket as any load purpose.
Is there any question in the name of Static Switch in UPS??
Grid fault level [KA]?
how to commissioning the genset with amf panel?
IN induction motor pf is increased using capacitors.what will be the effect on motor and system when very large capacitor is accidently installed and pf goes leading.
Why we use mho Relay in long transmission line?
define the active power?
What is meant by a stray loss of a induction motor??? What is the equation to find it
Define cut-off rate?
what is the criteria for selecting fuse rating in 1phase, 2phase & 3phase welding sets?
ELECTRICAL ENGINEER TEST IN FEWA ANY ONE HAVE KNOWLEDGE ABOUT THIS?????????
hi everybody how to design string combiner box (scb) internal parameters like bus bar and spd (surge protection device and fuse which place to set that,and also bus bar one particular cross sectional how much heat generated and how much power loss tell me Clearly and briefly
hi this is hema, r there any books in particular for the preparation of the APPSC-A.E.E(electrical), if so please mail me the names ... thank u .
what is mean by drives?
Describe the colour rendering properties of i) tungsten filament lamps ii) tubular fluorescent lamp