Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

How can we calculate the fault level of the distribution
system knowing the percentage impedance of transformer &
subsequent equipments.

Answer Posted / amar singh.

fault level depend on system impedance
full load current*100
Trasformer fault level= ----------------------------
%impedance of the transformer

Is This Answer Correct ?    51 Yes 17 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What are the uses of stepper motor?

1198


why we permissive overreach in distance protection.where it is applicable to use in long r short lines

2714


What is meant by cold loop test in instrument

2561


what is the significance of terminal voltage and phase sequence in the operation of paralleling of two generators?

2505


Define active filter?

973


what is the meaning of WYE and DELTA in Electric meter?

3783


What the difference between ac and dc inductor an capacitor

2364


block diagram of 2 ups system connected in parallel mode?

2047


Differentiate between ideal and non ideal current sources?

1113


explain the types of drives

1935


what is the safty of poly phase tranformer?

2085


How to calculate phase to phase difference ?

2207


What is the basis for selecting Vk/2 or Vk/4 for REF and Differential protection of Transformer and What is the significance of magnetising current

2334


I have a drawing of a wound rotor induction motor for a crane. This crane motor has 5 forward speeds & 5 reverse speed implemented of course with different amount of resistance for each speed setting selected. What has got me scratching around is the fact that 8 of the 10 speed selections switch in uneven (unbalanced) amounts of resistances on each of the 3 connections to the motor's rotor.Can this be possible? I would have assumed this would produce unbalanced rotor currents and therefore vibration in the motor. I would greatly appreciate anyone's comments on this. Many thanks, Confused.

1830


Practical condition in 400KV Sub station:- Breaker(open) , isolator(open), Earthing (close) at both end e.g A & B. Now Open A Stn Earthing than Open B stn Earthing (Which have a 50MVA reactor) , AND suddenly show R,Y,B phase 704KV,573KV,118KV respectively. Que is without closing of breaker how it is possible.???? My Whats app No:07621840498 for Further Discussion. Pls experts suggest.

2048