I have a problem with a valve (air to close).
When it is fully closed and try to open 1% it doesn't responce till 3% open suddenly more than 3% then back to 3%.
I tried to tune positioner then removed it, the problem still exist.
Any idea
Answer Posted / jigaranadkat
There can be may issues :
1) Very first indication is that your plug and seat are having some foreign particles or uneven surface which is restricting the valve for initial opening.
2) Check the springs of the actuator for any crack as when pressure is increased it lifts the valve.
3) Check for positioner relay.
Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
In my company plc based winders are operated. one day there was a data transmission failure alarm shown on pc. as per sir instruction we have reset master plc but winders were not triped and alarm gone. so what master plc do?
what effects a surging can produce in the compressor
what is gas metering system? gas chromatograph? and gas compressors?
what is the protection system in solar turbine compressor
applications of plc in printing and packaging?
how to calculate range of level transmitter?
Tr. Wiring for calibration.
How an rtd work, and what volts/current goes to a rtd to measure the resistance?
What is Positive Calibration and Negative Calibration?
What do you know about gail?
Why is it necessary to use compensation leg to measure the liquid level in a closed or pressurized tank?
What is hp & mp seperator .& what is its working principle ?
How it the difference between force balance system and dispalacement balance system?
I need to know steps to Calibration Valve Guard......
what is o2 analyzer and how it measured ,what is the role of this analyzer in cfbc boiler...