The formular of how to calculate a cross sectional cable to feed an electric motor.
Examle: 15KW, 26.1A, 415V. Calculate the cable size in mm2
Answer Posted / shridhar awasthi
Since it's an LT cable so in this case we can't apply the min cross sectional formula A=I square root t/K.
to find out the cross sectional area for this case fist find out the Load current which is given 26.01A. so refer the Manufacture cataloge and select the appropriate cable size for full Load current.
after selecting appropriate size of cable we will have to apply the derating factor according to the laying condition.
Now multiply that derating factor to cable ampacity,so we will get actual current carrying capacity of that cable.
Now for find our the no. of runs divide full load current to actual current capacity of cable after applying derating factor,so will get no. of runs.
now calculate voltage drop. if this in the permissible limit the our selection is right and if the V.d. is beyond the the increase the size of cross sectional area or no. of turns.
In this case 4 sqmm copper wire is sufficient for Star-delta starter.
Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
Does all the output contacts (N/O as well as N/C) of a Numerical relay operate when relay receives a binary input/inputs or contacts are designated to specific logic input/inputs and only these contacts operate?
what is solkor relay and which condition it will act?
Load transfer in 11kv double busbar switchgear - operation.
If an electrical component has a positive temperature coefficient, how come such components have high power losses due to heat if current decreases when resistance increases? assuming power given by I^2*R whereby the Resistance is infinite.
WHY NUTRAL GROUND SYSTEM USED IN 33KV SYSTEM
sir pls tell me . our ct specifications are 120/5 ,2 core , 0.2 and 5p10 class , 30va and 30va buden. insted of 30 va i want use 15 va. can i use?
Why neutral point is consider as zero potential?
What is minimum permicible value of leackage current for LT Panle when applying voltage up to 3 KV for 5 Minuits?
i have interview in Pepsi company what type of question will ask please send the question and answeer
what is the main parts of transformer? how it is functioning? pls giv the ans briefly.
What is essential to prove safe isolation of electrical circuit?
for 5KW resistive load can anyone please suggest me whether to go for UPS/Inverter or Generator depending upon cost calulations
how to calculate transformer turn primary & secondary side 11kv to 420v
in control scheme dc logic wiring commonly using negative loop,what is the reason?if we use positive looping what will happen?
What is the difference between UPS & inverter ? which UPS is better and whos got the edge ? what is the difference between & inverter ? which UPS is better and whos got the edge 12 V , 24 V , 36 V etc what are the advantages of 12 V, 24 V , 36 V etc and what are the disadvantages of 12 V, 24 V, 36 V etc thanks