I HAVE A 1 MVA TRANSFORMER, I WANT TO KNOW THE FAULT LEVEL OF
THE SYSTEM ( WHAT IS FAULT LEVEL PLEASE EXPLAIN WITH EXAMPLE)
Answer Posted / satyajit sadhu
FAULT LEVEL MEANS SHORT CIRCUIT CAPACITY OF TRANSFORMER.YOU
HAVE NOT MENTIONED THE VALUE OF TRANSFORMER RATIO & % OF
IMPEDENCE.ASSUMED VOLTAGE RATIO= 11KV/415 V & % OF
IMPEDENCE=6%.
RATED FULL LOAD AMP OUTPUT =1MVA/(415 X 1.732)=1391.25A
SO SHORT CIRCUIT CAPACITY OF TRANSFORMER= 1391.25/6%
=23187.44 A
IF ANY FAULT OCCURED THEN THE ABOVE TRANSFORMER WITHSTAND
THE SHORT CIRCUIT CURRENT OF 23187 A.
| Is This Answer Correct ? | 33 Yes | 4 No |
Post New Answer View All Answers
when 20hp 3 phase motor start no load condition in star or delta connection.find current and write formula.(tariq)
wheather the size of windings in motor and generator are the same
What is cross over distortion? How it can be eliminated?
although ckt breakers have taken the place of old fuse. But instead of it , these older ones are still used in the industries and homes ? why .... what are their advantages and disadvantages ? which one is leading and winning the race and competition ?
what is the IS foe lightning arrester?
I want to make street light with solar system ... What may I do for procedure and how much of estimation for each material ... If any one knows guide me and inform this id : aravindd7@gmail.com
different aspects of voltage stability
Why the frequency of ac in india is 50 hz but in some other countries it is 60 hz.
A ii kv 1200 A Breaker combination fixed in a cubicle. How many ampere Fuse is required? If fuse is not using, Why?
what is the importance of earthing system on the generators big capacity and small?
what is the difference between earthing and unearth
give single line diagram of D.G distribution form alternator to main L.T panel?
why Y CONNECTION IS BETTER INTERMS OF EFFICIENCY AND P.F FOR A LAOD LESS THAN 40% AND WHY AFTER DELTA IS BETTER FOR > 40%
Why 30kw 40 hp 4 pole 3ph induction motor over heated?any steps on reduction in heat?
WE ARE PLACE A NEW 75 KW MOTOR FOR JPF.IT IS CONNECTED IN M.C.C. WHEN WE ARE STARTING M.C.C.INCOMER IS TRIPPED.THEN WE ARE CONNECTED IN P.C.C WITH A MM30 RELAY PROTECTION THEN WE ARE STARTED MOTOR WILL RUN SMOOTHLY.