How can we calculate the fault level of the distribution
system knowing the percentage impedance of transformer &
subsequent equipments.
Answer Posted / jigar shah
suppose transformer (11 KV/433) is of 1000 KVA & %
impedance is 4 .LT side Fault level can be calculated as
below :
KVA = 1.732 X V X I X Cos Phi - PF assumed : 0.95
LT Rated current (I) = (1000 * 1000)/(1.732*433*0.95)
= 1481 A
Fault current on LT side = FLC * 100/(% impedance)
= 1481 * 100/5
= 29.62 KA
| Is This Answer Correct ? | 44 Yes | 54 No |
Post New Answer View All Answers
What are the components of feedback control system?
what is meant by power and distribution transformer ?
Does the motor power displayed on the Motor name plate is the mechnical power motor delivers or it is consumed power from the system?
while doing high voltage test on 11kv/433 distribution transformer why we only give 28 kv on hv side and 3kv on lv side for power transformers what is the value what factors it depends
We are designer please help me calculate the size of 11kv cables from step up transformer to M.V panel, total load is 5 mega watt distance 900 feet (used aluminum type cables) please provided formula for calculate the cable with example.
what is the difference between neutral and earth
How to select transmission line type (i.e. 11kv or 33kv) for new established industries
what is the differencce inn series and cascade connection??
Define what is difference between fuse and breaker?
battery capacity use of made?
What is load boxes ?
How to synchoronize the generator (with gcb,GT) to grid????? ????? from Grid iam getting power (rated 400kv/20kv) through GT and its goes to UAT.,,ST.,, now my generator(rated 20kv ) ready.,, now iam closing my GCB.,, in GT iam suddenly giving 20kv on that Gt.,, what will happend
how to control dc motor?
How to dimensioning SDCCH, LAPD and CS7 signaling on GSM?
what is the difference between rectifier and converter and commudator?