capacitor applied voltage is 1100VDC & capacitance value is
82uF how to calculate current of capacitor.
Answer Posted / chreamz
Basic Electrical Engineering
First Step: Calculate the Capacitance of the system
>> Frequency = 50 or 60 Hz
>> Xc = 1/ (2πfC)
= 1/ (2π*50*82µ)
= 1 / (2*3.141*50*82µ)
= 25.76 Ω
Final Step: Ohms Law
>> V = IXc
1100 = I*25.76
∴I = 42.702 Amps
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
what kind of technical test that i need to learn because i have an interview tomorrow.. please someone help me..
Why field rheostat is kept in minimum position?
what is an unbalance in acircuit? in a three phase 3wire circuit how an unbalance will come? in a three phase four wire system how an un balance is coming?
What are motor generator sets and explain the different ways the motor generator set can be used ?
is oil viscosity affect on motor current?
what is the effect of connecting three phase supply lines to three phase auto transformer output terminals through a fuse of 10Amp and a circuit breaker (MCB). Is this connection permanently destroy the transformer?
i applied for the ap transco please forward the freqventley asked QA
If a high resistance fault occurs,then what are the changes will happen in the system?
Why arc quenching is used in Diode ?
The height to which the liquid in a tank to be maintained for a certain constant velocity?
what is reverse power relay brief explanation and in b/w where it is connected
what is the minimum voltage require to injure our body?
What is different between Circuit breaker and Isolater?
11kv/433v delta/star distribution transformer primary side full load Ht current is 83.33A in , but input side VCB rating 800A.why?
ASTM D 3455 - Standard Test Methods for Compatibility of Construction Material with Electrical Insulating Oil of Petroleum Origin has been used for Testing Transformer Oils with a product placed in it. Aged Control Oil has a Power Factor of 0.032% at 100°C. Aged Oil with a Test component has a Power Factor of 0.093% at 100°. Is this increase acceptable? If not why? How much increase is acceptable?