can we replace a pressure transmitter of range 0 to 25
Kg/cm2 by a Pressure transmitter of range 0 to 10
Kg/cm2 ?.. Will it affect 4 to 20 mA output signal which we
will feed to the PLC.
Answer Posted / govind singh
Going by standards, 20 mA of first transmitter will read 25 kg/cm2 pressure, while same reading for second transmitter will be 10 kg/cm2. So at same pressure, both transmitters will send different current signals. So calibration at the DCS end will be needed.
Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
Why not come out analog output in ABB EL3020 when display show correct value
What is intrinsically safe system?
How to calibrate RC Feeder system in thermal power station?,If any instrument available to calibrate it,ple inform me. make:stock,
Name different parts of a pressure gauge.
any body please send me the old question papers of ongc test.
how we are selecting instuments by differentiating certain instruments in 4 to 20 ma range and certain in 1 to 5 v dc
What is the purpose of the analyzer in petrochemical plant?
how to calculate range of level transmitter?
what is isloted barrier how it works and what are the main purpose.how it make safe area.
To become an Instrument DESIGN engineer, is there any softwares or training to become Instrument Design engineer, plz suggest me, Iam very much interested in designing.
In dcs panel we are using diff type of modules ?what is module ? what is the use of modules ?diff type of module?
what is the calibration procedure for magnetic flow meter @ onsite
why we should maintain neutral earth voltage below 1V while calibration? why cant it be 1.2V or 2V
Reason for capillary type dp level transmitter fluctuation
what is diffrance between FF & SMART, explain with difination